Reply
RE: Buffers, hot water and cooling

I agree it seems like a lot of work particularly as its going to be needed for only a few days per year, at least for now ie until Climate change real...

1 month ago
Reply
RE: COP is not the only measure of efficiency

@jamespetts Lots of things to unpack here so I will confine my comments to a couple you may find helpful   With a Vaillant the set temper...

1 month ago
Reply
RE: Inventor (Midea) Heat Pump short cycling advice

True! I think so, or fit fancoils! From your figures the system is more for cooling than it is for heating.

1 month ago
Reply
RE: Inventor (Midea) Heat Pump short cycling advice

Do you mean kWh/day? Thats essentially nothing unless its just for DHW? You arent doing any material space heating on 2-4kWh/day! Is it possible y...

1 month ago
Reply
RE: Inventor (Midea) Heat Pump short cycling advice

Whoa. Is it also used for heating? If so then it needs to be sized to meet your heating demand. Also beware, some low output heat pumps are simply ...

1 month ago
Reply
RE: Inventor (Midea) Heat Pump short cycling advice

Yes but... it can only modulate so low. If the demand is less than the min modulation the water temperature will overshoot(heating)/undershoot(coolin...

1 month ago
Reply
RE: Inventor (Midea) Heat Pump short cycling advice

Your short cycling is occurring because the heat pump can't modulate down enough to match the demand. If you increase the system volume as suggested...

1 month ago