Joining the Renewable Heating Hub forums is completely free and only takes a minute. By registering you’ll be able to ask questions, join discussions, follow topics you’re interested in, bookmark useful threads and receive notifications when someone replies. Non-registered members also do not have access to our AI features. When choosing your username, please note that it cannot be changed later, so we recommend avoiding brand or product names. Before registering, please take a moment to read the Forum Rules & Terms of Use so we can keep the community helpful, respectful and informative for everyone. Thanks for joining!

JamesPa
JamesPa
@jamespa
Moderator
Illustrious Member
Joined: Apr 3, 2023
Last seen: Oct 20, 2026
Topics: 28 / Replies: 5524
Reply
RE: Twin 10kw Grant Aerona Volumiser Tanks using lots of power

Ok that's clearer. It's a pity about the manifold pumps, they effectively stop the ashp having the control it needs to make sure everything works pr...

2 years ago
Reply
RE: Twin 10kw Grant Aerona Volumiser Tanks using lots of power

Thanks, thats helpful. There seems to be a circular path around the upper volumiser, is this correct (it could be, perhaps the upper heat pump is the...

2 years ago
Reply
RE: New to world of ASHPs: Ideal Logic Air Monobloc heat pump 8kW questions

Only to the extent that the heat has been produced at a lower COP than your space heating. But as you are probably talking 1-2kWh max per day, who ca...

2 years ago
Reply
RE: Fujitsu Waterstage WOYG160LJL Air Source Heat Pump

This is indeed ambiguous!. One would expect, since this is in a section called 'room influence' that it means ambient in, but it is unclear. the ba...

2 years ago
Reply
RE: Twin 10kw Grant Aerona Volumiser Tanks using lots of power

Honestly, my first call would be to disable them. As I say above the main point of the volumisers is simply to add water volume (ie its a tank). The...

2 years ago
Reply
RE: New to world of ASHPs: Ideal Logic Air Monobloc heat pump 8kW questions

In fairness sometimes it's the only viable location. So long as gge pipes and tank are well insulated it may be the best that an be done. My cylin...

2 years ago
Reply
RE: Twin 10kw Grant Aerona Volumiser Tanks using lots of power

Sorry I misunderstood 55 to be the dhw temp not the flow temp for dhw. That being the case I wouldn't change it. It sounds like everything is basic...

2 years ago
Reply
RE: Twin 10kw Grant Aerona Volumiser Tanks using lots of power

Is there a setting allowing you to increase the differential between flow temperature and target dhw temperature. Then it would heat up quickly to a...

2 years ago
Reply
RE: Twin 10kw Grant Aerona Volumiser Tanks using lots of power

Thanks. I know a fair bit about heat pumps but not grant specifically, and I certainly dont know about their master slave setup. However i suspect t...

2 years ago
Reply
RE: Fujitsu Waterstage WOYG160LJL Air Source Heat Pump

You clearly have 'got' it. You dont really need me! The only thing Im not sure about is this "then reduce the temp set point on the ASHP down fro...

2 years ago
Reply
RE: Twin 10kw Grant Aerona Volumiser Tanks using lots of power

I apologies for my reaction. I was initially shocked that anyone would do this and then shocked that anyone makes it into a product. I still am TBH...

2 years ago