Joining the Renewable Heating Hub forums is completely free and only takes a minute. By registering you’ll be able to ask questions, join discussions, follow topics you’re interested in, bookmark useful threads and receive notifications when someone replies. Non-registered members also do not have access to our AI features. When choosing your username, please note that it cannot be changed later, so we recommend avoiding brand or product names. Before registering, please take a moment to read the Forum Rules & Terms of Use so we can keep the community helpful, respectful and informative for everyone. Thanks for joining!
Last seen: Nov 22, 2026
@ecoste Numerically, and i'm sorry if it's obvious to you already: 25L/min @ 2.0 DeltaT = ~3.5kW output so with ~1.17kW input it's a CoP ...
@ecoste what happens to DeltaT if you double your flow rate to 30L/min, via the pimary circ pump and also proportionally increase any other zone pumps...
@ecoste Here is mine for comparison on the same day: /p> 14 rads - two zones but running in simultaneouslyR410a 8.5kW unit, FTC5 generation
Thanks @ecoste , This should help @jamespa with his questions too Well, it appears to be running quite nicely, no cycling as you say... Flow rate on...
@ecoste are you willing to share your interactive MELPump Detailed Report from a sample day to help us analyse?
@toodles Not quite the case, NetZero is free (including the capacity monitoring) but things like automations and diagnostics are part of the NetZer...
On a slightly different topic, I had a calibration today and it's almost the 1y anniversary of the install Capacity at install was 13.7kW and now si...
Okay, thanks for explaining - it would be the former. The heat pump current state is always reported actual, regardless of attempts to change...
@majordennisbloodnok @boycey So to clarify, I don't belive that @boycey is using the dedicated MELPump CN105 Adapter and only using MELCloud integrati...
@boycey are you absolutely certain that Havenwise control has been relinquished..? It sounds very like the settings that it uses
I do mine dynamically - so here i start at 32C setpoint (3C outdoor) from my curve and then will increase dynamically as required up to the minimum wh...
I would say yes - the floor frequency is linked to outside temperature, so for example in my 8.5kW R410a monobloc unit at 0-5C outdoor the minimum fre...