RE: Ecodan Pump Issues… Circulation pump turns off when heat pump compressor turns off

@patch321 The recommended is 32L/min.... The range for the 11.2kW unit is 14.4 to 32.1l/min This may not pose a significant issue in compar...

1 day ago
Reply
RE: Ecodan Pump Issues… Circulation pump turns off when heat pump compressor turns off

Throwing ideas out there, to protect pipework if they use a particularly large primary circulation pump on the 11.2's and someone does increase the sp...

1 day ago
Reply
RE: Ecodan Pump Issues… Circulation pump turns off when heat pump compressor turns off

  This is the 'OUTLET' from the external unit yes (so flow, before 3 way valve), as the magnetic filter is shown just below  

1 day ago
Reply
RE: Ecodan Pump Issues… Circulation pump turns off when heat pump compressor turns off

@patch321 No, not standardThe valve below it is the end of the Pre-Plumbed cylinder, this has been fitted by your installer

2 days ago
Reply
RE: Advice for a novice on Mitsubishi Ecodan 6kW

  In the Home Assistant firmware the data points are between 2s and 25s depending how important the values are, e.g. compressor frequency, flow...

2 days ago
Reply
RE: Ecodan Pump Issues… Circulation pump turns off when heat pump compressor turns off

@patch321 You are going to have a bit of a fight on your hands I'm afraid if you are oversized and particularly in warm weather. the Ecodan logic...

2 days ago
Reply
RE: Ecodan Pump Issues… Circulation pump turns off when heat pump compressor turns off

@patch321 1. Why do the circulation pumps turn off soon after the compressor stops? In compensation curve or fixed flow, the result of a flo...

3 days ago
Reply
RE: Advice for a novice on Mitsubishi Ecodan 6kW

Frost Protect/Freeze Stat is an operation mode, where Defrost is a multi-stage status flag (however i only see two used).In the firmware i inject defr...

3 days ago
Reply
RE: Advice for a novice on Mitsubishi Ecodan 6kW

@sheriff-fatman It appears Output Power = 0kW because there was a DeltaT of 0Which doesn't appear correct because it was 4C according to the data.L...

3 days ago
Reply
RE: Melpump Users Anywhere?

A sneak preview of the onboard compensation curve designer that is going to be built into MELPump for use only with the adapter.Still tweaking the des...

2 weeks ago
Reply
RE: My Powerwall 3 Consumes 3-4 kWh/Day in Self-Consumption: Is This Normal?

I have done some investigation into this previously, I have 3 data sources - Tesla measurements (instantanious), Tesla App History and also some high ...

4 weeks ago
Reply
RE: Mitsubishi Ecodan R290 10kW performance

  It's generation dependent, the latest FTC7 (touchscreen) have the ability to modulate PWM based on OAT.  