Joining the Renewable Heating Hub forums is completely free and only takes a minute. By registering you’ll be able to ask questions, join discussions, follow topics you’re interested in, bookmark useful threads and receive notifications when someone replies. Non-registered members also do not have access to our AI features. When choosing your username, please note that it cannot be changed later, so we recommend avoiding brand or product names. Before registering, please take a moment to read the Forum Rules & Terms of Use so we can keep the community helpful, respectful and informative for everyone. Thanks for joining!

JamesPa
JamesPa
@jamespa
Moderator
Illustrious Member
Joined: Apr 3, 2023
Last seen: Aug 18, 2026
Topics: 27 / Replies: 5257
Reply
RE: Is My Midea Heat Pump Inherently Defective?

Just to say you do need a firm tap (occasionally several), just opposite the inlet to the radiator. Hit it about as hard as you dare. Sometimes this...

2 years ago
Reply
RE: How To Balance Radiators & the Role of the Lockshield Valve: A Homeowner's Guide

So deltaT across rad circuit = 37.9-24.4 = 13.5C. ~5C is what we are looking for. So Im expecting the return from rads to be more like 32C than 24...

2 years ago
Reply
RE: Is My Midea Heat Pump Inherently Defective?

Yes. If the pin feels sprung then no problem. If it moves freely then the closing piece (not sure what it's called) may be stuck. A few sharp taps ...

2 years ago
Reply
RE: Not a good January? My heat pump used 840 KWh of electricity

You adjust the end points of the sloped line.you presented earlier. This will be somewhere in the menu, probably the installer menu. I would reduce ...

2 years ago
Reply
RE: Not a good January? My heat pump used 840 KWh of electricity

Yes thanks, good plot Yes initially, but then you turn down the weather compensation curve until the house is at just the right temperature, that...

2 years ago
Reply
RE: Not a good January? My heat pump used 840 KWh of electricity

Situation normal then as @tim441 says you are almost certainly going to have to meddle if you want your system to work efficiently. T...

2 years ago
Reply
RE: Not a good January? My heat pump used 840 KWh of electricity

Black thing looks like (probably) a low loss header combining the output of the two pumps. You will get complete mixing in that which could in princi...

2 years ago
Reply
RE: How To Balance Radiators & the Role of the Lockshield Valve: A Homeowner's Guide

On the grounds that turning the pump speed down didnt help I would put it back up again. Slow flow = higher deltaT across radiators = higher FT neede...

2 years ago
Reply
RE: Not a good January? My heat pump used 840 KWh of electricity

Quite likely not but...with two pumps you have the opportunity to get a very good turndown/modulation ratio and a level of redundancy against failure....

2 years ago
Reply
RE: How To Balance Radiators & the Role of the Lockshield Valve: A Homeowner's Guide

Sorry thats lots of numbers, but no clear explanation what they are measuring. What is needed is the temperatures of flow to and return from the rad...

2 years ago
Reply
RE: ASHP & Radiator Sizing - Measuring Heat Loss

That's correct. You probably will need to measure flow rate though, spec sheet will likely just be a pump curve.

2 years ago