Joining the Renewable Heating Hub forums is completely free and only takes a minute. By registering you’ll be able to ask questions, join discussions, follow topics you’re interested in, bookmark useful threads and receive notifications when someone replies. Non-registered members also do not have access to our AI features. When choosing your username, please note that it cannot be changed later, so we recommend avoiding brand or product names. Before registering, please take a moment to read the Forum Rules & Terms of Use so we can keep the community helpful, respectful and informative for everyone. Thanks for joining!
Last seen: Aug 18, 2026
Why the Tado controls? Get rid of them and use the native Vaillant controller, the Tado controls will only harm efficiency.
@jeegnesh It’s all been explained to you already. Inactive is pure weather compensation mode, where the only sensor which affects flow temperature ...
@jeegnesh Your chosen set point temp is the desired indoor temperature that you choose via your SensoCOMFORT controller and myVaillant app. If you’r...
@jeegnesh Doesn’t matter which room temp mod mode you’re using; the following behaviour happens: During scheduled ‘heating’ periods, the heat pump t...
@jeegnesh Almost. Your heat pump has no idea about your ‘design temp’, which is just the result of a theoretical calculation used to specify your h...
@jeegnesh Check your 'setback temp' setting. This will dictate the desired set point temperature that your Vaillant will target outside of your normal...
@editor Thanks for this. So can we safely assume that the Green IQ setting does absolutely nothing at all, on or off, when used with an Arotherm Plu...
@editor Yes, we’ve read the guff in the manual, but that still doesn’t explain anything about what the setting actually does, if anything at all. A...
I'd also love to know!
@jwilliams89 The Energy Stats article should really be updated, it's misleading at the moment.
@jwilliams89 Yes, it is accurate. You can verify it by modifying your desired temperature and checking the new target flow temp on the controller.
@jwilliams89 The reason for asking is that the tables on the Energy Stats website are incorrect, and in a way so is the Vaillant manual. The actual ...
- 27 Forums
- 2,811 Topics
- 66.5 K Posts
- 1,841 Online
- 7,217 Members
Join Us!
Installer Finder
Degrees of Separation
Latest Posts
-
RE: Why don't people choose heat pumps?
It's swings and roundabouts - during off-peak periods t...
By Temperature_Gradient , 4 minutes ago
-
RE: The Changing Jet Stream Could Challenge UK Air Source Heat Pumps
... And that's being generous! I'll tell you a littl...
By SusannaSaunders , 6 hours ago
-
RE: Adding data centre electricity costs to domestic energy bills?
never ceases to amaze me.. Keeping steel works going ...
By Batpred , 7 hours ago
-
RE: Electricity price predictions
great session Reminds me why some politicians can be ha...
By Batpred , 7 hours ago
-
RE: Boiler Upgrade Scheme funding reduced by circa £750 million in 2026 budget
Absolutely agree. The massive Hager CU my vaillant requ...
By Batpred , 7 hours ago
-
RE: How much of your renewable and home setup would still work if the internet went down?
absolutely agree. even if many providers see that extra...
By Batpred , 8 hours ago
-
RE: Octopussy cosy 6 experience
People who have a Cosy appear generally to be happy wit...
By JamesPa , 11 hours ago
-
I thought the cr*p came first and the biofuel came afte...
By Majordennisbloodnok , 15 hours ago
-
RE: Aerotherm and weather compensation
@jamespa I replied yesterday with detailed readings whi...
By DavidB , 2 days ago
-
RE: Marvel Heating liquidation
@editor This is an important point. each winter, you...
By davidnolan22 , 3 days ago
-
RE: Solar Power Output – Let’s Compare Generation Figures
Very nice. we’ve been super soggy here, but rather m...
By Papahuhu , 3 days ago
-
RE: DIY powerflushing tutorial
Interesting! I toyed with the idea too. But I installed...
By bobflux , 4 days ago
-
RE: 15kw pump for 225m2 1990's house - over kill?
@seaviews Agree with the others on sequence: loft first...
By mk1234 , 4 days ago
-
RE: Vaillant ecoTEC Plus - Flow Temp and Set Up
Heating been on for 4 weeks now, continuous. It's 6C o...
By trebor12345 , 5 days ago