Joining the Renewable Heating Hub forums is completely free and only takes a minute. By registering you’ll be able to ask questions, join discussions, follow topics you’re interested in, bookmark useful threads and receive notifications when someone replies. Non-registered members also do not have access to our AI features. When choosing your username, please note that it cannot be changed later, so we recommend avoiding brand or product names. Before registering, please take a moment to read the Forum Rules & Terms of Use so we can keep the community helpful, respectful and informative for everyone. Thanks for joining!

Derek M
@derek-m
Member
Illustrious Member
Joined: Mar 4, 2021
Last seen: Sep 19, 2024
Topics: 7 / Replies: 4403
Reply
RE: 17kW Grant Aerona 3 - advice needed for pre-commissioning struggles

Without looking at the Grant manual, I assume that TM1 is the cold end setting for the weather compensation (WC). Whilst lowering this setting may sav...

4 years ago
Reply
RE: 17kW Grant Aerona 3 - advice needed for pre-commissioning struggles

When you state 'currently running with 40 degrees max', have you set 40C as the maximum permitted LWT?

4 years ago
Reply
RE: 17kW Grant Aerona 3 - advice needed for pre-commissioning struggles

@denevil What are the heat loss calculations and size of your home?

4 years ago
Reply
RE: Connecting to Midea MSmartHome using a PC

I don't think that the data is actually encrypted, more likely coded then decoded. You need to be aware that the serial data transmission is actuall...

4 years ago
Reply
RE: Mitsubishi Ecodan & Raspberry Pi automations

@kev-m Hi Kev, What is the setting of the Interval Timer?

4 years ago
Reply
RE: My ASHP is running out of hot water

Switch off the immersion heater at the wall switch, then using a small spanner remove the nut holding the cover in place. Underneath you should find t...

4 years ago
Reply
RE: Airwell/Midea unit not heating hot water after adjusting weather compensation

I would suggest that you check to see if your system is set for CH priority rather than DHW priority. If so, set it to DHW priority and schedule it fo...

4 years ago
Reply
RE: ashp and pv diverter working together

Electrical power diverters are excellent devices, we have had one connected to our system for quite a number of years. Because they use electronic c...

4 years ago
Reply
RE: My ASHP is running out of hot water

Hi Curly, Do you know where the cable supplying the on - off switch for the immersion heater is supplied from? Can you provide a closeup photo of yo...

4 years ago
Reply
RE: Heat pump delta T too low - 2c

The quantity of heat energy produced by a heat pump is given by the formula:- Q = mcDT Where Q = Heat Energy, m = Mass, c = Specific Heat Capacity...

4 years ago
Reply
RE: Latest NIBE model has known defect and no solution

I'm afraid if it was me, I would be making it abundantly clear that this is not acceptable, since you have now been without adequate heating for 6 wee...

4 years ago
Reply
RE: Mitsubishi Ecodan & Raspberry Pi automations

I would suggest setting the Interval Timer to 60 minutes to help reduce the cycling.

4 years ago