@cathoderay this is great news. I'm pleased we're getting somewhere. There's a noticeable step change in the power output starting with the 18:00 re...
Hello, Sounds like the flow goes through the magnetic filter before it gets to the PEX, so that's good. 22mm and 1.8m3/hr is about 1.3m/s. I thin...
A brief explanation of reading vendor pump curves. Here's a simple heating system. It's got 3 radiators, each one can be turned on or off separatel...
Something else crossed my mind when I posted on a discussion about the order components should installed. You mentioned you reversed the direction o...
Hello All,I'm conscious I've turned up on the forum and am writing these long posts full of apparent technical detail. I've been troubleshooting heat ...
Hello All, remember your designing a loop transferring liquid water. The pump just moves the liquid round in circles. It makes no difference to syst...
@cathoderay I'll put something together about pump curves and system curves. But to help you, I suggest the following: Open all the TRVs and locks...
Hello, I can explain all the pump curve information, but it will take a while for me to put some pictures together. For now, lets work on the basis t...
^Hey, look at that, it worked 🙂 OK, This is a pump curve. The top one shows Head against volumetric flow at different pump speeds. The chart show...
Hello again,I wonder what's going on here? The system seems to have landed at an equilibrium point. LWT = Set_LWT and the compressor has slowed do...
Hello,I'm not very good with using quotes from forum posts, so I'll try to use headings insted.How did I calculate the secondary flow rate?If you igno...
I found an install manual for an MD16IU-008DW unit. Can you find the value of dT1SH? It might be in "ServiceMan / 3. Heat mode settings" The manu...
- 26 Forums
- 2,112 Topics
- 46.4 K Posts
- 47 Online
- 3,408 Members
Join Us!
Latest Posts
-
RE: Wood burner with ASHP - direct air?
Hi Topher, Thanks for the tag Mars. I am.indeed o...
By Sune , 56 minutes ago
-
RE: No-code, plug-and-play monitoring for your heat pump
I think I have found “The One!” Waveshare ESP32-S3-POE-...
By Grantmethestrength , 14 hours ago
-
RE: Buffers, hot water and cooling
@prunus, @jamespa is correct, but removing the buffer ...
By Brendon Uys , 19 hours ago
-
@downfield and @toddles, this isn’t in the settings cur...
By Mars , 2 days ago
-
RE: Homely launched for Grant Aerona ASHP control
I haven't bought the Aerona Smart Controller (£700!) bu...
By Prunus , 2 days ago
-
RE: Antifreeze top up for my heat pump - is this a rip off?
For the record, Grant supply ethylene glycol for their ...
By Prunus , 2 days ago
-
RE: Compressor attempts start but fails - Nibe Fighter 2005 8kW
@skyefarmer amazing. Well done!
By Mars , 2 days ago
-
RE: Say hello and introduce yourself
Hi @topher - you might be interested to see this very r...
By Transparent , 3 days ago
-
RE: Air source heat pump roll call – what heat pump brand and model do you have?
Ebac 5kw - Monobloc R32. Developed and made in UK - Mit...
By marcinwloch69@gmail.com , 4 days ago
-
RE: Is a Valliant Inline 6kW heater a BUS buster?
Just another thought - it might be worth thinking about...
By JamesPa , 4 days ago
-
RE: BUS Grant: removal of all other fossil fuel heat sources
@rikiarn - just have a think as to how much it will cos...
By Transparent , 5 days ago
-
Don't do much digging around.That's best left to the pr...
By Transparent , 5 days ago
-
Hi all, I was wondering if anyone had an idea of how th...
By Wh0am3ye , 5 days ago
-
RE: EBAC re-entering the ASHP market in 2023
@toodles confirm i have Ebac 5kw ASAP + homely and it w...
By marcinwloch69@gmail.com , 5 days ago
-
RE: Compute heat loss from energy used
@jamespa Ebac must be similar to Mitsubishi as they buy...
By marcinwloch69@gmail.com , 5 days ago
-
@pie_eater I have been thinking of adding cooling to my...
By TechnoGeek , 7 days ago
-
RE: Victorian Semi Retrofit / Extension ASHP and UFH Advice
Agree, but you may have a hard time convincing them, as...
By JamesPa , 1 week ago
-
RE: Seal the Deal: Don't Let Your Heat Pump Leak Energy
Hi - fyi - there's a dead image link in the 'Optimal In...
By seatonian , 1 week ago
-
RE: Ripped Off: How UK Homeowners Are Paying Gas Prices for Wind Energy
@chandykris Horses and beggars…. 😉 Toodles.
By Toodles , 1 week ago
-
RE: Cleaning up after gas meter removed
@agentgeorge Likewise in the loft space; we have 300mm ...
By Toodles , 1 week ago