RE: 14kW Daikin Altherma HP, UFH: struggles to maintain delta T at LWT < 39-38 degrees Celsius

One of my [many] knowledge gaps. What is the right delta T? Should I vary this? If so, what are the parameters that should drive these changes? I ...

2 years ago
Reply
RE: 14kW Daikin Altherma HP, UFH: struggles to maintain delta T at LWT < 39-38 degrees Celsius

I found additional material for that journey here. "...Scroll compressors with continuous modulation can adjust from 10 to 100 percent capacity (or v...

2 years ago
Reply
RE: 14kW Daikin Altherma HP, UFH: struggles to maintain delta T at LWT < 39-38 degrees Celsius

@frappzy I can do the same on my. Mine is rated at 16kW. When I was "playing around/fine tuning" the flow temp and delta T I ended up with this [s...

2 years ago
Reply
RE: 14kW Daikin Altherma HP, UFH: struggles to maintain delta T at LWT < 39-38 degrees Celsius

I have been looking into this as well. I think this may have something to do with the capabilities of the inverter on the pump. From what I could fi...

2 years ago
Reply
RE: Our Grant Aerona R32 13kW ASHP installation

@allyfish I have this quandry as well. Is the additional wear and tear on the heat pump more or less in $$ than the electricity cost on the cheap rat...

2 years ago
Reply
RE: Air source heat pump problems - NIBE F 2040 ASHP

@rickk54 While I am new to heat pumps (just installed 16kW Samsung Gen6) - what I have learnt is that the carnot equation only has 2 parameters (Tem...

2 years ago
Reply
RE: Daikin monobloc energy usage

You should be able to video it frosted up. And if you monitor your flow temp, you should see a defrost cycle. My heat pump takes 3-4 mins to defrost....

2 years ago
Reply
RE: Heat pump delta T too low - 2c

@derek-m Exactly, I had this formula for UFH, though not sure it is correct but seems to give results in a reasonable ball park. In any case the resu...

2 years ago
Reply
RE: GSHP running UFH but no feedback loop yet.

@alistersmith I think it is important to get some basic monitoring in place [if you don't have it yet]. You don't need fancy stuff, but at least flow...

2 years ago
Reply
RE: Heat pump delta T too low - 2c

Of course, I should have been clear, I need to accurately know the dT with much more accurate sensors, but it was more to illustrate the point that mi...

2 years ago
Reply
RE: Heat pump delta T too low - 2c

@derek-m Yes, the flow rate "meter" in the pump is done via fancy calculations by the pump electronics. So probably some "fancy" filtering going on a...

2 years ago
Reply
RE: Low COP on Samsung 16kw Gen6

For now off the controller UI, manually put it in a spreadsheet. I have installed the modbus adapter in the unit outside, just not had a chance to co...

2 years ago
Page 14 / 18
Share:

Join Us!

Trusted Installers

Struggling to find a reliable heat pump installer? A poor installation can lead to inefficiencies and high running costs. We now connect homeowners with top-rated installers who deliver quality work and excellent service.

✅ Verified, trusted & experienced installers
✅ Nationwide coverage expanding
✅ Special offers available

👉 Find your installer now!

Latest Posts

x  Powerful Protection for WordPress, from Shield Security
This Site Is Protected By
Shield Security