@transparent We do not connect thermal stoor DHW units to the central heating. If you want a heat pump to work efficiently in heating mode, DO NOT con...
@bontwoody No need for air valves as long as the run lengths are not too long. You can tell if there is an air lock, there would be no flow on that ci...
Personally I like thermal stoors for heat pumps Advantages lower water temperature required, therefor better efficiency the entire cylinder is ...
@editor Be very cairfull, I have requested the data for the 3THERMO product as it is not on their website. Why, makes me question the capabilities of ...
Hi Mark It is very possable to install under floor heating on a wall. Spreader plates are a good idea, use 16mm pipe and keep the run lenths to arro...
@derek-m A couple of things to clarify but you have the concept. As many fully open heat emitters as possible, with limited use of TRV's and only u...
@derek-m This effect is normal at this time of year if you are running full weather compensation without suffucient thermal mass in your property, (mo...
@batalto As a trial, that is fine, however if you want to get the best performance, you need to optimize the entire system, not only the controller. Y...
@batalto If you want to control your system by switching it on and off instead of intelligently, that is your choice. You are paying the electricity b...
@markc Great news, it appears that my claims are being verified, however, you must remember that you are still compromising without removing un-needed...
@kev-m That may be Ok, Do you have the return temperature?
@witchcraft It is very difficult, if not impossible, to zone a property and get performance unless your heat delivery system in the area you are runni...
- 23 Forums
- 2,098 Topics
- 46.2 K Posts
- 79 Online
- 3,385 Members
Latest Posts
-
RE: Heating coming on when not required
@editor It may be that. I do remember setting up a max ...
By bontwoody , 18 minutes ago
-
RE: Heat pump solutions and/or installer recommendations for France
I’d travel to France for work if you were struggling wi...
By Damon Blakemore , 6 hours ago
-
RE: Pressure drop Primary circuit
Just to update you all. I made up my own fill loop as...
By ohdearism , 7 hours ago
-
RE: Ecodan consuming 100kwh per day in new build!!!
Hmm Before doing that I would want to be certain that...
By JamesPa , 11 hours ago
-
RE: 5 Star Service from Havenwise
That's always a danger with any new good idea, @morgan....
By Majordennisbloodnok , 11 hours ago
-
Have your say in the Renewable Heating Hub Awards
It’s time to celebrate the best (and call out the worst...
By Mars , 22 hours ago
-
-
RE: Mitsubishi cycling while on chilled water output
@iaack yes there's no denying that cold air sinks! I s...
By downfield , 1 day ago
-
RE: Weather compensated secondary circuits with Biomass
@andycoo that flooring sounds ideal. Extra volume is ...
By Sune , 1 day ago
-
If you are thinking of heating on the immersion conside...
By JamesPa , 3 days ago
-
RE: Surface mount or bury primaries for heat pump installation?
@tomasmcguinness, I think your best bet would be using ...
By Aventus Eco , 3 days ago
-
RE: Solar Power Output – Let’s Compare Generation Figures
@toodles all depends on asking the right questions! And...
By Tim441 , 3 days ago
-
RE: Commencing on an ASHP Installation Process
I received confirmation this morning that my Greener Ho...
By Sheriff Fatman , 3 days ago
-
@jamespa Thanks for the advice - very helpful. I had al...
By abam48 , 4 days ago
-
RE: Adding battery storage to SolarEdge PV system
@chandykris No need to apologise at all! I forgot to ad...
By Toodles , 5 days ago