RE: Grant Aerona3 13kW Noisy pipes after balancing

Thanks guys, I will open up the valves again and check the dipper switches when I get home tomorrow. Quick follow up question, if the flow has been li...

3 weeks ago
Reply
RE: Grant Aerona3 13kW Noisy pipes after balancing

@johnr This what I find a bit confusing, I thought that if the temps are the same or a small DT then no heat is leaving the emitter it is just flushin...

3 weeks ago
Reply
RE: Grant Aerona3 13kW Noisy pipes after balancing

The reason I tried to balance the system is that I have no confidence in the install. I know you are meant to run the system as wide open as possible ...

3 weeks ago
Reply
RE: Grant Aerona3 13kW Noisy pipes after balancing

Cheers @toodles I suspect that some of this install is merely “new” to us! I am currently looking at building my own homely “clone” using Home Assist...

3 weeks ago
Reply
RE: Grant Aerona3 13kW Noisy pipes after balancing

Cheers @Toodles, the flow rate at the minute is roughly 25/26 l/min (such a rubbish gauge!) flow temp 36c, return 33c and the pump is belting out 4,30...

3 weeks ago
Reply
RE: Grant Aerona3 13kW Noisy pipes after balancing

Well after a quick run around, bled the rads again (should have done that after I found another leak yesterday mid balancing!). I have opened all the ...

3 weeks ago
Reply
RE: Grant Aerona3 with Octopus Cosy tariff

@jamespa Thanks for the words of encouragement I dialled down the weather comp to 38c @ 0c last night and even though it was 0 outside the house neve...

4 weeks ago
Reply
RE: Controversial opinions - pure weather compensation, buffer tank, heat loss, oversized heat pumps

@uk_pete_2000 no worries I am really standing on the shoulders of giants here and just trying to get it to work for me so happy to share.

1 month ago
Reply
RE: Is the Grant controller a thermostat?

@davidm06 a bit more detail here.

1 month ago
Reply
RE: Is the Grant controller a thermostat?

@uk_pete_2000 Sorry I should have explained better that is the reading off the modbus register 33 “indoor temperature master actual” which I think is ...

1 month ago
Reply
RE: Grant Aerona3 with Octopus Cosy tariff

@uk_pete_2000 to be honest we are still learning so trying to find the best place for it however this is mainly redundant now as we have moved over to...

1 month ago
Page 1 / 2
Share:

Join Us!

Heat Pump Dramas?

Thinking about installing a heat pump but unsure where to start? Already have one but it’s not performing as expected? Or are you locked in a frustrating dispute with an installer or manufacturer? We’re here to help.

Pre-Installation Planning
Post-Installation Troubleshooting
Performance Optimisation
✅ Complaint Support (Manufacturer & Installer)

👉 Book a one-to-one consultation now.

Latest Posts

x  Powerful Protection for WordPress, from Shield Security
This Site Is Protected By
Shield Security