Joining the Renewable Heating Hub forums is completely free and only takes a minute. By registering you’ll be able to ask questions, join discussions, follow topics you’re interested in, bookmark useful threads and receive notifications when someone replies. Non-registered members also do not have access to our AI features. When choosing your username, please note that it cannot be changed later, so we recommend avoiding brand or product names. Before registering, please take a moment to read the Forum Rules & Terms of Use so we can keep the community helpful, respectful and informative for everyone. Thanks for joining!

Derek M
@derek-m
Member
Illustrious Member
Joined: Mar 4, 2021
Last seen: Sep 19, 2024
Topics: 7 / Replies: 4403
Reply
RE: Kev-M's ASHP Performance

@kev-m Hi Kev, One further area were it may be possible to reduce energy consumption by a few percent, would be by tightening the 'heat pump ther...

5 years ago
Reply
RE: Kev-M's ASHP Performance

@kev-m Hi Kev, Having ambient air temperatures around 2C is not very good for ASHP operation, because it will increase the number of defrost cycl...

5 years ago
Reply
RE: ASHP in Hampshire

@batalto Hi Batalto, Your ASHP will still operate, even if the temperature measurements are not accurate. From the point of view of the heat ener...

5 years ago
Reply
RE: ASHP in Hampshire

Hi Batalto, I am not trying to prove anyone wrong. My objective in producing the spreadsheets, was for people to have a model, showing how their sys...

5 years ago
Reply
RE: ASHP in Hampshire

@batalto In the spreadsheet the required water flow temperature is calculated based upon your heat loss data, your estimated total heat output from...

5 years ago
Reply
RE: ASHP in Hampshire

The spreadsheet that I produced and sent to you some time ago, incorporated the data that you provided about your system. At an ambient temperature of...

5 years ago
Reply
RE: Kev-M's ASHP Performance

Hi HR_3, I'm afraid it is not quite as simple as watts per m2. Your heat loss will probably vary from room to room, rooms with larger window area wi...

5 years ago
Reply
RE: ASHP in Hampshire

Hi Batalto, Based upon the Midea data that you supplied previously, along with your heat loss calculations and heat emitter data, the energy consump...

5 years ago
Reply
RE: Kev-M's ASHP Performance

@kev-m Hi Kev, For clarity, could you please identify which readings you think are incorrect, is it the ones on the MMSP or the FTC controller? A...

5 years ago
Reply
RE: 11.2kW Mitsubishi Ecodan replacing LPG boiler

@rv3 Hi RV3, I think that it should be possible for you to get better efficiency, lower energy consumption and a higher COP, if you optimise your...

5 years ago
Reply
RE: Kev-M's ASHP Performance

@kev-m Sorry Kev, I did not make myself clear in the earlier message. If you look through pages 6 through to 9 for the MMSP flowmeter, it shows how...

5 years ago
Reply
RE: Kev-M's ASHP Performance

@kev-m Hi Kev, I think that you said before that you don't have a buffer tank, but do you have a low loss header? Do you have any pumps in addi...

5 years ago