Joining the Renewable Heating Hub forums is completely free and only takes a minute. By registering you’ll be able to ask questions, join discussions, follow topics you’re interested in, bookmark useful threads and receive notifications when someone replies. Non-registered members also do not have access to our AI features. When choosing your username, please note that it cannot be changed later, so we recommend avoiding brand or product names. Before registering, please take a moment to read the Forum Rules & Terms of Use so we can keep the community helpful, respectful and informative for everyone. Thanks for joining!
Last seen: Sep 19, 2024
You may also wish to take a night school course in 'Samsung speak' before considering one of their systems. 😎
To calculate the required LWT based upon the WL slope settings. The ambient air temperature in your case is 20C minus -3C = 23C. The set LWT range...
@craig1980 The video below shows where the Teva_out sensor is located and how it can be tested.
Because you only desire an indoor temperature of 18C, you can leave your thermostats set to 21C. The inverter pump to which the message refers is on...
Not quite correct. With your above settings, the WL slope is from a LWT of 20C at an ambient of 20C, up to a LWT of 32C at an ambient of -3C. So if ...
As far as I am aware, you go into Field Setting Mode, as you did when you obtained the data previously.
Hi Craig, I have been giving the page from the manual that you posted, a closer inspection, and although, in typical Samsung fashion, the text is abo...
@batalto I hope that you have resolved your problem, the grid needs all the help that it can get at the moment.
Hi Craig, Is your system working? What are the present settings of #2091, #2092 and #2093?
Hi Craig, When you changed to fixed LWT, I believe that you also changed the setting for the External Room Thermostat, 2091 or 2092. I suggest that...
You monitor the results on the four 7-segment displays in the bottom left hand section of the circuit board. Pressing the K4 switch repeatedly will ta...
@craig1980 Hi Craig, I think that this manual covers your model, and seems to show the same tests on page 40 onwards.
- 27 Forums
- 2,808 Topics
- 66.3 K Posts
- 2,216 Online
- 7,211 Members
Join Us!
Installer Finder
Degrees of Separation
Latest Posts
-
RE: Marvel Heating liquidation
Sorry to hear about this. I dont have personal experi...
By JamesPa , 19 minutes ago
-
RE: The Changing Jet Stream Could Challenge UK Air Source Heat Pumps
@susannasaunders I agree with @jamespa, I think that yo...
By Rob of York , 2 hours ago
-
Boiler Upgrade Scheme funding reduced by circa £750 million in 2026 budget
The funding for the BUS grant appears to have been subj...
By Rob of York , 3 hours ago
-
RE: Vaillant ecoTEC Plus - Flow Temp and Set Up
JamesPa The chart explains well how the heat curve an...
By trebor12345 , 6 hours ago
-
RE: Free app: run the immersion / heat pump from Growatt battery & solar surplus – no Home Assistant
Please bear in mind, everyone, that in order to use thi...
By Majordennisbloodnok , 1 day ago
-
RE: The good, the bad and the not that great – my heat pump installation
@burtis Thanks for posting this and Im so pleased you ...
By JamesPa , 1 day ago
-
RE: I need help with Ecodan ASHP
@f1p It turns out there have been a solar panel install...
By Andris , 2 days ago
-
RE: 15kw pump for 225m2 1990's house - over kill?
@seaviews your installer would be right to say that the...
By GrahamF , 2 days ago
-
RE: Tradespeople on Their Phones: What’s Acceptable When They’re Working in Your Home?
Actually, that's a very important point. I've only ev...
By Majordennisbloodnok , 2 days ago
-
RE: Aerotherm and weather compensation
These are likely inked. The basic explanation is tha...
By JamesPa , 2 days ago
-
RE: Electrical works for air to air heat pump
agree with above. I have not had extra costs added wh...
By Batpred , 2 days ago
-
Good to hear that you found a solution. Absolutely a...
By Batpred , 2 days ago
-
RE: Are there any comparisons of DHW heat stores around?
@sarahemmm I have done things the opposite way round I ...
By Toodles , 3 days ago
-
RE: How will removing the standing charge on gas bills benefit heat pumps?
The BUS grant funding for 2026/27 will run out at the c...
By Rob of York , 4 days ago