Joining the Renewable Heating Hub forums is completely free and only takes a minute. By registering you’ll be able to ask questions, join discussions, follow topics you’re interested in, bookmark useful threads and receive notifications when someone replies. Non-registered members also do not have access to our AI features. When choosing your username, please note that it cannot be changed later, so we recommend avoiding brand or product names. Before registering, please take a moment to read the Forum Rules & Terms of Use so we can keep the community helpful, respectful and informative for everyone. Thanks for joining!
Last seen: Apr 8, 2025
I've just checked the heat loss calculation for my system (7kW Arotherm+) and it estimated 8.3kW at -2.8C. I reckoned that was high compared with the ...
You should also be able to set an outside air temperature at which the system will turn off.
According the the Vaillant app, my 7kW Arotherm+ produced 7.6kW when the outside temperature was -7C.
My 7kW Arotherm+ normally runs at 1200 litres/hour but I've seen it show 1800 litres/hour when doing the DHW. It may also use the latter speed when ge...
Some points arising from comments above: 1. The heat pump can't defrost and produce heat at the same time. It's the process of extracting heat from ...
That looks good. I note the best practice of first fitting the pipe insulation and then clamping the insulated pipe to the wall - something that my in...
Winter is a bad time for solar generation. This past winter has been gloomier than normal and if your panels aren't facing south or are vulnerable to ...
I've also got some potentially relevant data because I bought a pair of Elitech recording temperature sensors and fixed them to the flow and return pi...
Definitely not A or G which are in the DHW circuit as that creates a lot more water to heat up to DHW temperature when heating the DHW. My buffer tank...
50 litres/p> But a flow temperature of less than 35C must be a major contributor to the good COP.
I think you should be aiming for lower (<40C) flow temperatures and an SCOP nearer 5. You might need some bigger radiators than currently proposed ...
I'll rock the boat as I've got a buffer tank as part of an installation of similar size to what is proposed and reckon that it's one factor in getting...
- 27 Forums
- 2,813 Topics
- 66.6 K Posts
- 2,064 Online
- 7,223 Members
Join Us!
Installer Finder
Degrees of Separation
Latest Posts
-
RE: Adventures in heat loss calculations
@rob-of-york In my experience, energy used to supply DH...
By Toodles , 1 hour ago
-
RE: Should Households Who Can Afford It Pay More for Energy to Help Those Who Can't?
@mars Whatever method of alleviating the high cost of e...
By Toodles , 1 hour ago
-
Grant Aerona - Weather Compensation and Schedules
Im trying to set up a friends Grant Aerona. The WC curv...
By bontwoody , 2 hours ago
-
RE: Why don't people choose heat pumps?
Absolutely nothing in the regs prevents this, nor does ...
By JamesPa , 11 hours ago
-
RE: Air-to-Air Heat Pumps & Air Conditioning: UK Heating and Cooling Q&A
@jamespa I agree, the efficiency of Cosy Cooler ought...
By Rob of York , 11 hours ago
-
RE: How much of your renewable and home setup would still work if the internet went down?
I think you're right! 🤨
By Transparent , 23 hours ago
-
RE: Renewables & Heat Pumps in the News
ECO4 muddies the water somewhat, and then some. I thi...
By cathodeRay , 24 hours ago
-
RE: Vaillant ecoTEC Plus - Flow Temp and Set Up
If there is a drain nearby that's exactly what I would ...
By JamesPa , 1 day ago
-
RE: DIY powerflushing tutorial
This is what bacterial growth in UFH loops looks like. ...
By Pirate Rich , 1 day ago
-
I think that CCGT plant in Lingen is more likely to suc...
By Transparent , 2 days ago
-
RE: Heat Geek installations: share your experiences
@l8again fwiw my experience (Valiant but not with heat ...
By JamesPa , 2 days ago
-
RE: How Can I Prove Coal Was My Main Heating Source Without Receipts?
@etchedpixels thank you for the advice paid cash all...
By Chilli304 , 3 days ago
-
RE: The Changing Jet Stream Could Challenge UK Air Source Heat Pumps
@susannasaunders An interesting conversation to have ...
By Rob of York , 4 days ago
-
RE: Electricity price predictions
@rob-of-york sounds like a term that Heidegger would...
By Papahuhu , 4 days ago
-
RE: Adding data centre electricity costs to domestic energy bills?
never ceases to amaze me.. Keeping steel works going ...
By Batpred , 5 days ago