Joining the Renewable Heating Hub forums is completely free and only takes a minute. By registering you’ll be able to ask questions, join discussions, follow topics you’re interested in, bookmark useful threads and receive notifications when someone replies. Non-registered members also do not have access to our AI features. When choosing your username, please note that it cannot be changed later, so we recommend avoiding brand or product names. Before registering, please take a moment to read the Forum Rules & Terms of Use so we can keep the community helpful, respectful and informative for everyone. Thanks for joining!

JamesPa
JamesPa
@jamespa
Moderator
Illustrious Member
Joined: Apr 3, 2023
Last seen: Aug 25, 2026
Topics: 27 / Replies: 5282
Reply
RE: Heat pumps and on/off working - starting to quantify it

Consumption is entirely dependent on house construction. My house, a 1930s solid wall build with about 70% retrofitted IWI, 30cm loft insulation, d...

3 years ago
Reply
RE: moving from ASHP to Gas Combi

I agree with those who say don't/you cant do it, see regulation 5.4. The only 'get out' is that this is guidance which, 'in the opinion of the Sec...

3 years ago
Reply
RE: New Build - Grant Aerona3 10kW - Questions and observations

I don't have the full specs to hand (Grrant don't publish them AFAIK, but Chofu, the oem, might) however a 4:1 turn down for an a2w pump is a good fig...

3 years ago
Reply
RE: Vaillant Arotherm Plus Help needed

All a2w heat pumps work this way so far as I know, because it makes sense, Vaillant is no different. Ditto gas boilers with weather compensation. O...

3 years ago
Reply
RE: Vaillant Arotherm Plus Help needed

I guess that in principle, with the right plumbing, you could run both together at the ft of the dhw. Lousy efficiency and the output is divided betw...

3 years ago
Reply
RE: Vaillant Arotherm Plus Help needed

And gas boiler that operates weather compensation does exactly the same, for the simple reason that you need a higher flow temp for dhw than for space...

3 years ago
Reply
RE: ASPH Sizing Confusion

Yes mine also. It seems a sensible approach to me, much more sensible than making DT across each emitter the same in a system where the aim is to ope...

3 years ago
Reply
RE: ASPH Sizing Confusion

I completely agree. However DT can only change by a small amount (~5C) in a tolerably well adjusted setup and each degree it changes is equal to half...

3 years ago
Reply
RE: ASPH Sizing Confusion

I think because 6-8kW, which a 22mm pipe can deliver at a typical DT of 5, gives a sufficiently fast recovery time for many people and... 22mm gives...

3 years ago
Reply
RE: ASPH Sizing Confusion

Well exactly that. Much of the discussion above focussed on 'delta T' being in this case the difference between flow and return temperatures. But th...

3 years ago
Reply
RE: ASPH Sizing Confusion

I must say that the recent posts about buffers are most encouraging. When I first embarked on this journey it seemed almost heresy to suggest on a pu...

3 years ago
Reply
RE: ASPH Sizing Confusion

Because it's been done in a completely muddle headed way. The requirement for accessing a grant has been conflated with both planning and building re...

3 years ago