Joining the Renewable Heating Hub forums is completely free and only takes a minute. By registering you’ll be able to ask questions, join discussions, follow topics you’re interested in, bookmark useful threads and receive notifications when someone replies. Non-registered members also do not have access to our AI features. When choosing your username, please note that it cannot be changed later, so we recommend avoiding brand or product names. Before registering, please take a moment to read the Forum Rules & Terms of Use so we can keep the community helpful, respectful and informative for everyone. Thanks for joining!

JamesPa
JamesPa
@jamespa
Moderator
Illustrious Member
Joined: Apr 3, 2023
Last seen: Sep 21, 2026
Topics: 27 / Replies: 5416
Reply
RE: How much radiator capacity do I need for an air source heat pump?

Each Jaga rad has its own temp sensor and fan controller. There is no central connection to the heat pump. Same with Mitsi and just about every othe...

2 years ago
Reply
RE: How much radiator capacity do I need for an air source heat pump?

Not a real problem. If the rad output is correct at the design FT and design OAT, then it will also be (almost) correct at the lower FT determined...

2 years ago
Reply
RE: How much radiator capacity do I need for an air source heat pump?

Ah, that makes sense and the 7kW Vaillant plus backup is a strategy a neighbour of mine has, so far successfully, adopted. Note that at -2 the 7kW Va...

2 years ago
Reply
RE: How much radiator capacity do I need for an air source heat pump?

It wasn't supposed to be a criticism, just additional info. If you are building a spreadsheet, which many do, a formula is more useful than a table! ...

2 years ago
Reply
RE: How much radiator capacity do I need for an air source heat pump?

Many manufacturers give an equation in the following form: output is proportional to (deltaT)^n where deltaT is the mean difference between the ...

2 years ago
Reply
RE: How much radiator capacity do I need for an air source heat pump?

First question, what's the heat loss of your house? If by any chance you have a smart meter and can get half hourly or daily gas consumption you can...

2 years ago
Reply
RE: Thinking of ripping our my IVT Greenline HT Plus C model and replacing with a gas boiler.

Further to the above I found the manual here Page 37 describes the alarm and possible reasons, of which a blocked filter is one. Page 2...

2 years ago
Reply
RE: Thinking of ripping our my IVT Greenline HT Plus C model and replacing with a gas boiler.

Do you know what the alarm means. From what you 'have been told' it sounds like a 'low flow' alarm. If it wasnt there initially then something ...

2 years ago
Reply
RE: Is My Midea Heat Pump Inherently Defective?

As a former local government employee (following a career in engineering) I realised that explaining the consequences to politicians simply and in ter...

2 years ago
Reply
RE: ASHP and how it should run and potential kw consumption?

I am planning on trialling night time 'set forward' to take advantage of cheap rate tarrif. I have no idea if it will work in practice. The challeng...

2 years ago
Reply
RE: Is My Midea Heat Pump Inherently Defective?

Thanks for that, I think there is much comfort to be drawn because of: ... with which, based on everything you have told me, I agree. My heat ...

2 years ago