@marzipan71 You may befit from replacing the valve, it will depend on the current flow rate and system design. If you have a buffer tank, it will prob...
The ground loop pump must run when the heating is on, it may be a connection problem or the board has failed. You can as a temporary measure try conne...
It is quite possible to install a high temperature heat pump, and you can run it at high temperatures if you want to double your heating bill. However...
@derek-m Correct but the best way to control flow is automatically with equipment that can do it for you. If your system does not have Delta T contro...
@soniks Firstly, the engineers at Grant need to buy a new calculator or go back to school. 50 L/min will transmit 28Kw. You only need to transmit abou...
@soniks As I said, 28 mm will be fine, a 28 mm pipe has an internal diameter of 26.2 mm, the Grant 17 Kw will produce about 14 Kw at -2 at 50 odd degr...
@soniks change 28 mm primaries--- wrong, I have 30Kw heat pumps on 28 mm primaries very successfully Buffer tank--- Wrong in any circumstance unless...
@kev-m I understand where you are coming from, but it is wishful thinking. The industry did try to do exactly what you are asking and came up with the...
@derek-m Oh I wish. Unfortunately, we follow behind a myriad of idiots that blow your assumptions out the water.
@kev-m Unfortunately you are Oh- So-Wrong. If the builders had followed the building regulations over the last 30 years, you may be right, but they ha...
- 26 Forums
- 2,360 Topics
- 53.5 K Posts
- 215 Online
- 6,026 Members
Join Us!
Worth Watching
Latest Posts
-
Easiest solution is a surface mounted thermocouple, thi...
By AgentGeorge , 22 minutes ago
-
RE: New Fogstar 15.5kWh upright solution
May I pick up this comment from last week? As I under...
By Transparent , 32 minutes ago
-
RE: Mitsubishi Ecodan R290 10kW performance
Interesting. Thanks for the info.That would explain th...
By Sheriff Fatman , 1 hour ago
-
RE: My Powerwall 3 Consumes 3-4 kWh/Day in Self-Consumption: Is This Normal?
@f1p Might be normalmy numbers 3+ year old powerwall 2,...
By ksim , 4 hours ago
-
RE: Octopus Cosy Heat Pump Owners & Discussion Thread
The FT levels off at either the set point OR the minimu...
By AndrewJ , 15 hours ago
-
RE: MyVaillant Connect Regular Disconnect
Thanks. Yes, if the time is consistently 11pm every nig...
By buckwem , 15 hours ago
-
RE: Speedcomfort radiator fans
My take on Speedcomfort radiator fans: If anyone w...
By Mars , 21 hours ago
-
RE: Midea ASHP – how to set weather compensation
@pash44pump I have yet to come across any Clivet or Mid...
By benson , 22 hours ago
-
RE: Who's your electricity provider and what's your tariff?
@transparent Thanks, this helps. Could it be that St...
By Batpred , 22 hours ago
-
RE: Clivet ASHPs and weather compensation
Simon did share a lot of very helpful advice. On furthe...
By ambris , 22 hours ago
-
RE: Home Assistant vs ESPAltherma.
@majordennisbloodnok Thanks very much.
By Ubert767 , 23 hours ago
-
RE: Setback savings - fact or fiction?
I could, but I think we can do better, by plotting hour...
By cathodeRay , 2 days ago
-
RE: Advice on internal circulation pump noise
Extend the primary branch and make sure you have more t...
By ASHP-BOBBA , 2 days ago
-
RE: External pipework insulation
Oh Dear! that's appalling pipe work, should've been in ...
By dgclimatecontrol , 2 days ago
-
RE: Jokes and fun posts about heat pumps and renewables
By Morgan , 2 days ago
-
RE: Controlling Daikin Altherma via P1P2 and Home Assistant
On the contrary, @toodles, that’s a lot of help. I’d ne...
By Majordennisbloodnok , 2 days ago
-
Parsnip, Bacon & Coconut Milk Soup
First let me say, I am only a cook because I am human a...
By Toodles , 3 days ago
-
RE: Electricity price predictions
Ben Watts posted on LinkedIn that he had updated this w...
By Judith , 3 days ago