Joining the Renewable Heating Hub forums is completely free and only takes a minute. By registering you’ll be able to ask questions, join discussions, follow topics you’re interested in, bookmark useful threads and receive notifications when someone replies. Non-registered members also do not have access to our AI features. When choosing your username, please note that it cannot be changed later, so we recommend avoiding brand or product names. Before registering, please take a moment to read the Forum Rules & Terms of Use so we can keep the community helpful, respectful and informative for everyone. Thanks for joining!
Last seen: Aug 31, 2026
@ian33a — I have a sort of residual interest in this problem as I used to have an oil tank (and boiler) and I remember how vague my usage measurements...
I agree, and that is in effect what @jamespa and I have been doing! That's for the link and it seems I have been teaching grandmothers to suck eg...
@ian33a — a measured heat loss always trumps a calculated (whatiffery spreadsheet) heat loss, providing certain requirements are met. Firstly, the I...
Yes, see below. They are just standard regression lines, just as in any spreadsheet, but in R you have more control and more options, but as I have sa...
Using past oil usage to estimate heat loss is tricky. Firstly it is very unusual to have accurate interval usage. You fills your tank and runs your ...
@jamespa — this version may be marginally better:
@jamespa — the 0900 2100 IAT/OAT data is now in R and as a starter for ten I have distinguished between setback and setback and hour, 0900 and 2100, b...
@peterwurmsdobler — thank you for your positive comments. You are certainly taking a diligent and sensible approach to assessing your own needs. The...
@jamespa — as a taster, which may in fact already have given us the answer, here is the plot for the whole dataset (no setback/no setback sub sets) fo...
The mean (over the entire range of values) difference is only 20.57 - 19.28 = 1.29°C. At lower OATs this does indeed increase, as the drop in IAT duri...
I do lean to the idea that the main way setbacks save energy is by lowering the daily mean IAT. With careful timing, my setbacks start at 2100 which i...
And finally, the mean daily IAT against mean daily OAT plots. I have broken my 'Y axis must start at zero' rule because on this occasion is may make s...
- 27 Forums
- 2,754 Topics
- 64.7 K Posts
- 457 Online
- 7,159 Members
Join Us!
Installer Finder
Degrees of Separation
Latest Posts
-
RE: Adding additional Solar Panels to a DC coupled battery system
Let's deal with mounting systems first. You don't hav...
By Transparent , 5 hours ago
-
RE: How Accurate Is My DIY Heat Loss Calculation?
@kilgorexv definitely a larger inverter will help and m...
By AndrewJ , 23 hours ago
-
RE: Adventures in heat loss calculations
@rob-of-york — thanks for posting this, all very useful...
By cathodeRay , 1 day ago
-
RE: Surface mount or bury primaries for heat pump installation?
The installation is almost done! I've written up two ...
By tomasmcguinness , 2 days ago
-
RE: Glass lined Cylinder for private water supply
This has turned into a fascinating little rabbit hole. ...
By Mars , 2 days ago
-
RE: Switch suitable to change between two inverter CT's
Last winter my battery ,32KWh, could run the house com...
By Jancold , 2 days ago
-
RE: HeatGeek vs Octopus surveys: puzzling disparity - any ideas why?
Agree with Major. And even if I was very happy with ...
By Batpred , 2 days ago
-
RE: Is the "divide by 2900" rule still valid?
There is another estimator that you could use, a formul...
By Rob of York , 2 days ago
-
RE: To re-pipe or not to re-pipe? Moving from oil boiler to air source heat pump.
@penval, really useful update. After all the discussion...
By Mars , 4 days ago
-
RE: Who's your electricity provider and what's your tariff?
@papahuhu I prefer to look at it simplistically. We d...
By Old_Scientist , 5 days ago
-
RE: Questions about A2A for heating as well as cooling
@rob-of-york I would concur with the underfloor insulat...
By Toodles , 5 days ago
-
RE: New Vaillant Arotherm controls link to existing thermostats ; wired vs wireless
Nothing attached! I have rads but UFH makes the case ...
By JamesPa , 5 days ago
-
RE: Cooling with air to water heat pumps
Passive cooling should always be the first call. Keep ...
By JamesPa , 5 days ago
-
RE: Do I add Air Con or MVHR to existing A2W ASHP?
@rob-of-york Thank you, I’m thinking along these same l...
By Toodles , 6 days ago