Joining the Renewable Heating Hub forums is completely free and only takes a minute. By registering you’ll be able to ask questions, join discussions, follow topics you’re interested in, bookmark useful threads and receive notifications when someone replies. Non-registered members also do not have access to our AI features. When choosing your username, please note that it cannot be changed later, so we recommend avoiding brand or product names. Before registering, please take a moment to read the Forum Rules & Terms of Use so we can keep the community helpful, respectful and informative for everyone. Thanks for joining!

Tasos
@tasos
Member
Trusted Member
Joined: Nov 25, 2024
Last seen: Mar 20, 2026
Topics: 0 / Replies: 87
Reply
RE: Testing new controls/monitoring for Midea Clone ASHP

Thanks for recent data. Here are some more questions. I apologize, I am not using DHW and I am not familiar with schedules. What is your exact sc...

2 months ago
Reply
RE: Testing new controls/monitoring for Midea Clone ASHP

@benson Thanks for new graph. Initial reaction is that fluctuation of the various quantities is quite inexplicable and needs some more parameters to b...

2 months ago
Reply
RE: Testing new controls/monitoring for Midea Clone ASHP

@benson Indeed they do fluctuate more than I would expect. Perhaps a plot with set LWT, OAT and IAT would be more enlightening.

2 months ago
Reply
RE: Testing new controls/monitoring for Midea Clone ASHP

@benson I see, I misunderstood obviously. So you set LWT according to OAT, but not in WCC mode. You don't intend to use IAT using similar logic, I p...

2 months ago
Reply
RE: Testing new controls/monitoring for Midea Clone ASHP

I meant the following rule you mentioned using: "second automation will adjust this outlet flow temp value if needed. For example, if the IAT is out...

2 months ago
Reply
RE: Testing new controls/monitoring for Midea Clone ASHP

What you are actually implementing is a closed loop control idea, rather than the "open loop" WCC curve approach. It has been my postulate all along t...

2 months ago
Reply
RE: Midea ASHP – how to set weather compensation

Well, because there is a considerable delay in sensor information. This could have a serious effect on the performance of the closed loop system, such...

2 months ago
Reply
RE: Midea ASHP – how to set weather compensation

Hi all. I have also observed the strange behavior regarding LWT and T1s. By monitoring the relevant values I noticed, that if I calculate the T1s base...

2 months ago
Reply
RE: Testing new controls/monitoring for Midea Clone ASHP

@cathoderay OK, thanks all. Much as I thought. I am using the same logic. As for the Midea expert, I very much doubt there exists one.

3 months ago
Reply
RE: Testing new controls/monitoring for Midea Clone ASHP

Hi all, I need your help again, because of the lack of clarity of Midea'a manuals. Here is my question: If one employs an external room thermostat (...

3 months ago
Reply
RE: Testing new controls/monitoring for Midea Clone ASHP

@jamespa My god you've gone into great depth to make things work for you. I wonder why this limit is not adjustable. Anyway, thanks again, I am not ...

3 months ago
Reply
RE: Testing new controls/monitoring for Midea Clone ASHP

@jamespa Thanks for replying. Fan coil units in Greece are indeed used for cooling in the summer, with the appropriate hardware. The main reason I a...

3 months ago