Joining the Renewable Heating Hub forums is completely free and only takes a minute. By registering you’ll be able to ask questions, join discussions, follow topics you’re interested in, bookmark useful threads and receive notifications when someone replies. Non-registered members also do not have access to our AI features. When choosing your username, please note that it cannot be changed later, so we recommend avoiding brand or product names. Before registering, please take a moment to read the Forum Rules & Terms of Use so we can keep the community helpful, respectful and informative for everyone. Thanks for joining!
Last seen: Nov 15, 2026
@robs Quick response while I'm in stationary traffic leaving Anfield. This doesn't explain why the cycling behaviour at 5°C is so distinctive to tha...
Are you trying to address any particular performance issue with the system at the moment? What prompted the desire to look at flow rate to begin with...
Hi and welcome to the forums.Does your system use a Mitsubishi cylinder or is it a 3rd party one?The FTC6 settings from 1-5 only work on Mitsubishi cy...
I've been thinking along similar lines to @tim441 from my own experiences with an Ecodan system, where I've got the benefit of reported COP data too. ...
In my case it was a very specific pattern of behaviour at an OAT of 5°C that I could only attribute as being related to freeze stat function that I ob...
They show up as two distinct processes within MelPump, so I can see the two independently of each other. Within the HA settings you'll see the Defros...
Thanks for clarifying. Excessive cycling seemed to be a factor for me when I hit the 5°C and 4°C temperatures where freeze stat protection kicks in. ...
I don't intend to hijack the main thread but are you aware of a way to reset the daily totals from doing this? I set up integrations of this kind a f...
Great to read a good service story.I know that there are priority lists held for households with vulnerable customers in them. Perhaps your household...
Fair point. The highest frequency of defrosts I'd seen so far had been 6 within a 24 hour period, but my sample size of relevant data is very small. ...
In Ecodan world there are two bits of terminology that are easily confused.Anti-freeze protection (which MelCloud shows as a running mode as Freeze St...
Just realised that this image of the cylinder cupboard also includes the location of the Ecodan's flow sensor (as I've just discovered from a part lis...