Reply
RE: Electricity Tariffs for ASHP owners

@editor I was going to offer a similar observation. You need quite some thermal mass to keep the house warm through those peak hours during the winter...

2 years ago
Reply
RE: Electricity Tariffs for ASHP owners

At the Fully Charged show a few weeks ago I was chatting to the heat pump expert on the Octopus Energy stand. He said that they are planning to releas...

2 years ago
Reply
RE: PV without battery storage?

@heat-pump-newbie Correct. I have the simple but well built Solic200. Principle is exactly the same as the other devices like the iBoost but a bit old...

2 years ago
Reply
RE: Significance of delta betweeen flow and return temperature

@adaml I worked it, I scrolled through the overview settings, I’d left this lot alone until now. 8-06 looks to be 3. Have I read that correctly? Is th...

2 years ago
Reply
RE: Significance of delta betweeen flow and return temperature

@adaml I don’t know how to get to that value. It’s not in a menu option. Is it only available via laptop access? The installer manual has this

2 years ago
Reply
RE: Significance of delta betweeen flow and return temperature

@adaml yes. I’ve had to learn because the installer didn’t know what he was doing…

2 years ago
Reply
RE: Significance of delta betweeen flow and return temperature

@adaml I don’t have the option to set a maximum modulation value, for some reason that menu option doesn’t show. It’s the 11kw Altherma monobloc, the ...

2 years ago
Reply
RE: Significance of delta betweeen flow and return temperature

Picking up this significance of deltaT topic again but from the opposite side. My system is an Daikin Altherma 11kw Monobloc, described in other thr...

2 years ago
Reply
RE: Daikin Altherma 3M in Buckinghamshire

@bridgetjohn Set the disinfection to run to 60C for 10mins, it doesn’t need to be longer than this. I would also set this to run at 3pm on the day ...

2 years ago
Reply
RE: Daikin Altherma 3M in Buckinghamshire

@bridgetjohn as you have a third party thermostat (the Honeywell unit) the heating schedule will be set on that.

2 years ago
Reply
RE: Daikin Altherma 3M in Buckinghamshire

@bridgetjohn can you get a photo of the top of the grey volumiser tank in your cupboard please? There should be an automatic air bleed valve on the to...

2 years ago
Reply
RE: Daikin Altherma 3M in Buckinghamshire

@heat-pump-newbie it’s a large volumiser tank, I used to have one fitted on my system. It’s used in place of a backup heater, to ensure minimum volume...

2 years ago