AI Assistant
Activity
 
Notifications
Clear all

Joining the Renewable Heating Hub forums is completely free and only takes a minute. By registering you’ll be able to ask questions, join discussions, follow topics you’re interested in, bookmark useful threads and receive notifications when someone replies. Non-registered members also do not have access to our AI features. When choosing your username, please note that it cannot be changed later, so we recommend avoiding brand or product names. Before registering, please take a moment to read the Forum Rules & Terms of Use so we can keep the community helpful, respectful and informative for everyone. Thanks for joining!

fosterl2
@fosterl2
Member
Active Member
Joined: Feb 2, 2026
Last seen: Feb 24, 2026
Topics: 1 / Replies: 15
Reply
RE: Ecodan Cascade System Problem: DHW Heating Stops UFH & Pool Output

The next challenge will be getting 60mCu of water warmed up! - I assume for the initial heating, take the weather compensation off, fix both flow temp...

2 months ago
Reply
RE: Ecodan Cascade System Problem: DHW Heating Stops UFH & Pool Output

@f1p Indeed - I am just waiting to see if I get sent a bill for removing the cascade, but intend to either ask for a refund, or a return of my propert...

2 months ago
Reply
RE: Ecodan Cascade System Problem: DHW Heating Stops UFH & Pool Output

The issue seems to be solved: I found that the plumbers had routed the flow return from ASHP1 into the flow return of ASHP2, hence the whole system wa...

2 months ago
Reply
RE: Ecodan Cascade System Problem: DHW Heating Stops UFH & Pool Output

@f1p Just checked again (with different glasses on!) and they are sliders, not rockers, and set correctly. Looks like separating the cascade will be...

2 months ago
Reply
RE: Ecodan Cascade System Problem: DHW Heating Stops UFH & Pool Output

I am pretty sure that on mine, they are set the other way - the ones that are supposed to be ON have the sticking up bit up at ON side, and are presse...

2 months ago
Reply
RE: Ecodan Cascade System Problem: DHW Heating Stops UFH & Pool Output

So, if the rocker is down at the ON side and up on the OFF side, it is ON? Yes I do have Home Assistant, but it is using the MELCloud integration to...

2 months ago
Reply
RE: Ecodan Cascade System Problem: DHW Heating Stops UFH & Pool Output

I looked at the dip switches on the FTC 7s today. On my units, they are tiny rocker switches, rather than slide up / down. Is the dip switch "on" when...

2 months ago
Reply
RE: Ecodan Cascade System Problem: DHW Heating Stops UFH & Pool Output

I believe there is a single sensor mid-tank - this is the label on the tank This is yesterday's daily graph from MELCloud  

2 months ago
Reply
RE: Ecodan Cascade System Problem: DHW Heating Stops UFH & Pool Output

Are you saying "Plan B" is sound, i.e. separate the two, but just make sure the settings of both individual units match, or the cascade is sound? If...

2 months ago
Reply
RE: Ecodan Cascade System Problem: DHW Heating Stops UFH & Pool Output

@ashp-bobba If it is not possible in cascade to have 1 unit doing UFH & pool and one doing DHW + UFH / pool when not doing DHW, then plan B is to ...

2 months ago
Reply
RE: Ecodan Cascade System Problem: DHW Heating Stops UFH & Pool Output

@f1p The graphs do show there is about a 3 degree an hour loss of heat, and that is with very little hot water being drawn off - a morning wash, and a...

2 months ago
Reply
RE: Ecodan Cascade System Problem: DHW Heating Stops UFH & Pool Output

@f1p I am fighting one battle at a time here... hoping to get someone to say for definite if the SW 1-3 on the second pump is off, it should not then ...

2 months ago
Page 1 / 2
Share:

Join Us!

Latest Posts

Members Online

Click to access the login or register cheese
x  Powerful Protection for WordPress, from Shield Security PRO
This Site Is Protected By
Shield Security PRO