Joining the Renewable Heating Hub forums is completely free and only takes a minute. By registering you’ll be able to ask questions, join discussions, follow topics you’re interested in, bookmark useful threads and receive notifications when someone replies. Non-registered members also do not have access to our AI features. When choosing your username, please note that it cannot be changed later, so we recommend avoiding brand or product names. Before registering, please take a moment to read the Forum Rules & Terms of Use so we can keep the community helpful, respectful and informative for everyone. Thanks for joining!

fosterl2
@fosterl2
Member
Eminent Member
Joined: Feb 2, 2026
Last seen: Nov 12, 2026
Topics: 2 / Replies: 19
Reply
RE: Buffer tank on a 2 x 14kw Ecodan system

@JamesPa WRT the DHW: I am happy that is working OK and the heat loss is acceptable. The circulation pump runs so that there is always hot water at th...

1 day ago
Reply
RE: Buffer tank on a 2 x 14kw Ecodan system

@bobflux Yes, the motorised 3-way valve is for DHW. See schematic below – I thought it was worth doing a decent one for you good people helping, and f...

2 days ago
Reply
RE: Buffer tank on a 2 x 14kw Ecodan system

This is the energy consumed since September... ...throughout the period, the pool has been heated to the same 29c.

2 days ago
Reply
RE: Buffer tank on a 2 x 14kw Ecodan system

Here is the tank labelled up, and it is a 45lt tank, so I think no stratification is possible. Yes, the pool is being heated to 29c with a thermal...

2 days ago
Topic
Reply
RE: Ecodan Cascade System Problem: DHW Heating Stops UFH & Pool Output

The next challenge will be getting 60mCu of water warmed up! - I assume for the initial heating, take the weather compensation off, fix both flow temp...

9 months ago
Reply
RE: Ecodan Cascade System Problem: DHW Heating Stops UFH & Pool Output

@f1p Indeed - I am just waiting to see if I get sent a bill for removing the cascade, but intend to either ask for a refund, or a return of my propert...

9 months ago
Reply
RE: Ecodan Cascade System Problem: DHW Heating Stops UFH & Pool Output

The issue seems to be solved: I found that the plumbers had routed the flow return from ASHP1 into the flow return of ASHP2, hence the whole system wa...

9 months ago
Reply
RE: Ecodan Cascade System Problem: DHW Heating Stops UFH & Pool Output

@f1p Just checked again (with different glasses on!) and they are sliders, not rockers, and set correctly. Looks like separating the cascade will be...

9 months ago
Reply
RE: Ecodan Cascade System Problem: DHW Heating Stops UFH & Pool Output

I am pretty sure that on mine, they are set the other way - the ones that are supposed to be ON have the sticking up bit up at ON side, and are presse...

9 months ago
Reply
RE: Ecodan Cascade System Problem: DHW Heating Stops UFH & Pool Output

So, if the rocker is down at the ON side and up on the OFF side, it is ON? Yes I do have Home Assistant, but it is using the MELCloud integration to...

9 months ago
Reply
RE: Ecodan Cascade System Problem: DHW Heating Stops UFH & Pool Output

I looked at the dip switches on the FTC 7s today. On my units, they are tiny rocker switches, rather than slide up / down. Is the dip switch "on" when...

9 months ago