Joining the Renewable Heating Hub forums is completely free and only takes a minute. By registering you’ll be able to ask questions, join discussions, follow topics you’re interested in, bookmark useful threads and receive notifications when someone replies. Non-registered members also do not have access to our AI features. When choosing your username, please note that it cannot be changed later, so we recommend avoiding brand or product names. Before registering, please take a moment to read the Forum Rules & Terms of Use so we can keep the community helpful, respectful and informative for everyone. Thanks for joining!

Derek M
@derek-m
Member
Illustrious Member
Joined: Mar 4, 2021
Last seen: Sep 19, 2024
Topics: 7 / Replies: 4403
Reply
RE: How to turn ASHP heating off!?

@tufty I suspect the main item that would likely be damaged would the the condenser, which is a Plate Heat Exchanger (PHE). Whilst I don't think tha...

3 years ago
Reply
RE: Are you planning to use a wood burner to supplement your central heating this winter?

No. But not having a wood burner may have something to do with the decision. For some reason 'she who must be obeyed' frowns upon me trying to build a...

3 years ago
Reply
RE: How to turn ASHP heating off!?

I have no idea how long it will take or the likely cost. I have an A2A heat pump which doesn't require anti-freeze.

3 years ago
Reply
RE: ASPH Sizing Confusion

@bontwoody There are quite a number of aspects to consider when it comes to the sizing of a heat pump. As James has correctly pointed out, the sta...

3 years ago
Reply
RE: How to turn ASHP heating off!?

@tufty I suppose that this is one of the grey areas, where one would hope that the engineer would at least explain the meaning of the -4, before he ...

3 years ago
Reply
RE: ASPH Sizing Confusion

Where did you get the data for the Ecodan? According to the manufacturers data at an OAT of -7C, the 11.2kW Ecodan has a capacity of 10.6kW at a LWT o...

3 years ago
Reply
RE: Heat pumps and on/off working - starting to quantify it

@jamespa Hi James, I have now completed some further improvements to the modelling tool. It is now possible to adjust the desired IAT setpoint a...

3 years ago
Reply
RE: Ecodan ASHP cycling every couple of hours

@crustydoodle The installer is responsible to provide you with a proven functioning system, failure to do so would be a breach of contract. I would ...

3 years ago
Reply
RE: Ecodan ASHP cycling every couple of hours

From the noise point of view I seem to think that the water pump is being supported by the pipework. The pump should be mounted on a suitable bracket ...

3 years ago
Reply
RE: Samsung ASHP scheduling help

@redzer_irl You could try running the heat pump in fixed LWT mode starting with a low LWT setting and gradually increasing the setting until the des...

3 years ago
Reply
RE: Ecodan ASHP cycling every couple of hours

@crustydoodle Just to clarify if my understanding is correct. You started the heating system by raising the setting on one or more thermostats. Th...

3 years ago
Reply
RE: Ecodan ASHP cycling every couple of hours

Yes, the sensors are the thermistors. When I refer to 'good thermal contact', I mean is the thermister either fitted in a suitable pocket or clamped...

3 years ago