Joining the Renewable Heating Hub forums is completely free and only takes a minute. By registering you’ll be able to ask questions, join discussions, follow topics you’re interested in, bookmark useful threads and receive notifications when someone replies. Non-registered members also do not have access to our AI features. When choosing your username, please note that it cannot be changed later, so we recommend avoiding brand or product names. Before registering, please take a moment to read the Forum Rules & Terms of Use so we can keep the community helpful, respectful and informative for everyone. Thanks for joining!
Last seen: Mar 2, 2025
@derek-m nearly done. Doing it now.
@mike-h I have two small tanks above the uvc but I'm assuming they aren't buffer tanks? I have a cold water header tank in the loft and the system out...
Outside unit heat pump fans run for around 5 mins then it's quiet until 8 mins and 20 seconds then it starts again.
But at the beginning of the 8 min cycle they are both within 0.5 degree of each other at 22
Just checked flow and return temps on rad closest to UVC and it's 25.2 -22.6
Images of all figures and settings on the field settings manual. I hope it makes sense? It is on for exactly 7 mins 58 second and off for exactly 20...
@derek-m I'm just doing the monitoring now. Where would I find the LWT? I'm assuming that's leaving water temp? I have my thermometer now
@derek-m no problems, it's just something I'd seen before but wasn't sure if it was correct.
I have my doubts over this section. Could this be set incorrectly? Its set the same for this and external thermostat application #1 (flo...
I'll do that today and report back. Thanks
Still cycling at 8 mins on 20 seconds off with room stats at 25 degrees. Water outlet (flow temp I assume) is up a couple of degrees but the outside t...
Great, thanks. This is all very helpful