Activity
 
Notifications
Clear all

Joining the Renewable Heating Hub forums is completely free and only takes a minute. By registering you’ll be able to ask questions, join discussions, follow topics you’re interested in, bookmark useful threads and receive notifications when someone replies. Non-registered members also do not have access to our AI features. When choosing your username, please note that it cannot be changed later, so we recommend avoiding brand or product names. Before registering, please take a moment to read the Forum Rules & Terms of Use so we can keep the community helpful, respectful and informative for everyone. Thanks for joining!

Craig1980
@craig1980
Member
Estimable Member
Joined: Nov 23, 2022
Last seen: Mar 2, 2025
Topics: 5 / Replies: 141
Reply
RE: 12kW Samsung gen 6 short cycling

Interestingly, when I put the settings back to WC I get error E121. Upon looking this up in the manual it says "Short-or open- circuit error of the...

3 years ago
Reply
RE: 12kW Samsung gen 6 short cycling

Okay, many thanks for all of your help. I'll update if I find anything from Samsung. Thanks again. Much appreciated.

3 years ago
Reply
RE: 12kW Samsung gen 6 short cycling

Right, finished timing. Now back to 8 mins on 20 seconds off again. Flow temp 28.1 set to 30 Indoor 22.1 Outdoor 6.5 Room temp 19

3 years ago
Reply
RE: 12kW Samsung gen 6 short cycling

@derek-m none. I've just followed what it said in the video link that I sent then set to 35 now set to 30 and timing shut downs as it has turned on an...

3 years ago
Reply
RE: 12kW Samsung gen 6 short cycling

Room temp is slowly climbing. Up to 19 now.

3 years ago
Reply
RE: 12kW Samsung gen 6 short cycling

Measurements in brackets are on 35 flow temp setting.

3 years ago
Reply
RE: 12kW Samsung gen 6 short cycling

So, it appears to run constantly but at quite high power usage of 1.9kw instantaneous power. Rads feel warmer to the touch but room temp stays at a...

3 years ago
Reply
RE: 12kW Samsung gen 6 short cycling

Okay, that's done. It was already on standard temperature "water outlet". Could that have been an issue?

3 years ago
Reply
Reply
RE: 12kW Samsung gen 6 short cycling

I'm struggling to find where to switch to fixed LWT mode. 🙈 Although, whilst looking through the manual I found the page about removing the room sta...

3 years ago
Reply
RE: 12kw Samsung gen 6. Short cycling

@derek-m overnight it was 4 degrees and it has struggled to keep 18. The house is at 17.5 this morning. COP is down to 3.3 and it's using more power a...

3 years ago
Page 5 / 13
Share:

Join Us!

Latest Posts

Click to access the login or register cheese
x  Powerful Protection for WordPress, from Shield Security PRO
This Site Is Protected By
Shield Security PRO