Joining the Renewable Heating Hub forums is completely free and only takes a minute. By registering you’ll be able to ask questions, join discussions, follow topics you’re interested in, bookmark useful threads and receive notifications when someone replies. Non-registered members also do not have access to our AI features. When choosing your username, please note that it cannot be changed later, so we recommend avoiding brand or product names. Before registering, please take a moment to read the Forum Rules & Terms of Use so we can keep the community helpful, respectful and informative for everyone. Thanks for joining!

cathodeRay
cathodeRay
@cathoderay
Moderator
Famed Member
Joined: Feb 28, 2022
Last seen: Oct 26, 2026
Topics: 18 / Replies: 3076
Reply
RE: 14kW Midea ASHP in an old leaky building

Current (0915h) flow/return temps and top middle rear panel rad temps: Midea controller: Ambient: 7; LWT 47; RWT 41 PHE pipework: Primary in 45; p...

5 years ago
Reply
RE: 14kW Midea ASHP in an old leaky building

This gets complicated. Firstly there is the nominal output, as listed in the catalogues, usually at a delta t of 50. A correction factor then has to b...

5 years ago
Reply
RE: 14kW Midea ASHP in an old leaky building

@derke-m - Argghhh!!!! The forum has just deleted my reply. very frustrating. 'Something went wrong with your submission' or words to that effect, and...

5 years ago
Reply
RE: 14kW Midea ASHP in an old leaky building

@derek-m - OK, here are some minute by minute readings, col head abbreviations as before, csv text format. Ambient throughout was 5 degrees: Time,LW...

5 years ago
Reply
RE: 14kW Midea ASHP in an old leaky building

@mookyfoo - Midea promote themselves as being value for money, based on economies of scale, they are a huge company. They also promote themselves on t...

5 years ago
Reply
RE: 14kW Midea ASHP in an old leaky building

@batalto - I think they may have photographed the board, they certainly photographed other parts of the system. I have to be mindful that if something...

5 years ago
Reply
RE: 14kW Midea ASHP in an old leaky building

@mookyfoo - two 16kW heat pumps is certainly plenty of redundancy in a house with a heat loss of around 13.5kW! If two are really necessary, one would...

5 years ago
Reply
RE: 14kW Midea ASHP in an old leaky building

@derek-m - I don't know the model of the PHE, only its's make (Secespol) which is on the foam insulating jacket, which can't be removed without damage...

5 years ago
Reply
RE: 14kW Midea ASHP in an old leaky building

1800 hours: bedroom 17.5 (vs 19) bathroom 20.0 (vs 22) kitchen 17.4 (vs 19). All have benefited from recent solar gain, especially bathroom and kitche...

5 years ago
Reply
RE: 14kW Midea ASHP in an old leaky building

@batalto - I'm currently on the standard Freedom weather com curve, 55@-2/37@15. Bumping up the top end will do even nastier things to my COPs and is ...

5 years ago
Reply
RE: 14kW Midea ASHP in an old leaky building

@batalto - my provisional conclusions are that the problem, or part of the problem, the PHE may also be partly to blame, is the nominal 14kW Midea hea...

5 years ago
Reply
RE: 14kW Midea ASHP in an old leaky building

@batalto - yes, in effect, I had my full room by room heat loss calcs from when I first designed installed the CH in the 1980s, and I also had the hea...

5 years ago
Page 253 / 258