RE: Compressor and Evaporator Stratification

Thank you. That's an excellent find. As you can probably see I know nothing about the mechanics of how HP work. Looking at the diagram how many diff...

3 weeks ago
Reply
RE: Hitachi Yutaki SCombi Heat Pump - Thermal Off's

Thank you this is very helpful. There is a lot to take in. I have the heating on today and have been doing videos of the Live View. The funny thin...

4 months ago
Reply
RE: Hitachi Yutaki SCombi Heat Pump - Thermal Off's

I have tried the DT mode and it does seem to be better with this setting. The Gundfros UPM3 is current in constant pressure setting 3 (max). When t...

4 months ago
Reply
RE: Hitachi Yutaki SCombi Heat Pump - Thermal Off's

UFH is mainly 200mm. Screed - 17mm Ambi Tak. Mainly engineered wood and carpet and tiles.Grundfos UPM3 (K) in constant pressure mode. Switched on b...

4 months ago
Reply
RE: Hitachi Yutaki SCombi Heat Pump - Thermal Off's

It has taken me a while to get my head around it, plus the warmer temperatures to prove it. I have tried to explain the situation to Hitachi, but they...

4 months ago
Reply
RE: Hitachi Yutaki SCombi Heat Pump - Thermal Off's

Thank you all for your help, this has been a learning experience. So in summary. My heat pump is oversized, this causes Thermal Off’s or short cycle...

4 months ago
Reply
RE: Hitachi Yutaki SCombi Heat Pump - Thermal Off's

I am drawing the same conclusion that this system for some reason switches off for 3 minutes then 8 minutes latter does it's de-ice cycle. It does th...

4 months ago
Reply
RE: Hitachi Yutaki SCombi Heat Pump - Thermal Off's

8 room thermostats are all in Frost Protection mode. The one in the family room controls the heating. All the manifold actuators have been removed. ...

4 months ago
Reply
RE: Hitachi Yutaki SCombi Heat Pump - Thermal Off's

Your calculation of 13W per sqm fits well with what I found at 14W. So if I require 14W/m2 and the floor area is 179m. 179x14 = 2505. Does that m...

4 months ago