Joining the Renewable Heating Hub forums is completely free and only takes a minute. By registering you’ll be able to ask questions, join discussions, follow topics you’re interested in, bookmark useful threads and receive notifications when someone replies. Non-registered members also do not have access to our AI features. When choosing your username, please note that it cannot be changed later, so we recommend avoiding brand or product names. Before registering, please take a moment to read the Forum Rules & Terms of Use so we can keep the community helpful, respectful and informative for everyone. Thanks for joining!
Last seen: Nov 25, 2026
To quantify the greater pressure drop of your corrugated pipe you could try using an online calculator like For example, at 20 l/min a 25.4mm corrug...
Yes, your figures correlate well with your heat pump having a minimum output of about 3kW at these outside temperatures. Have you tried your heat pump...
You have clearly found your system's sweet spot! Yes, radiator based systems are likely to be limited in stable low flow temperatures. But larg...
I'm pretty sure it just means output, using the word capacity in this way isn't unusual in Japanese documents (and if something has a capacity then it...
As far as I know yes.
@johnmo The effect of cycling is very different with different heating systems too. If modulation was not an important factor heat pumps would still...
@tomasmcguinness Mitsubishi's figures are in(I'd suggest downloading it and reading it offline as it's a 400+ page PDF). For their new R290 ASHPs se...