Joining the Renewable Heating Hub forums is completely free and only takes a minute. By registering you’ll be able to ask questions, join discussions, follow topics you’re interested in, bookmark useful threads and receive notifications when someone replies. Non-registered members also do not have access to our AI features. When choosing your username, please note that it cannot be changed later, so we recommend avoiding brand or product names. Before registering, please take a moment to read the Forum Rules & Terms of Use so we can keep the community helpful, respectful and informative for everyone. Thanks for joining!

iancalderbank
@iancalderbank
Contributor
Prominent Member
Joined: Oct 17, 2022
Last seen: Jan 14, 2025
Topics: 0 / Replies: 643
Reply
RE: Heat pump delta T too low - 2c

@william1066 I think you've misread the diagram. you read across at 1 l/sec and select any kvs line within the shaded area. My purple line. higher k...

3 years ago
Reply
RE: Connecting to Midea MSmartHome using a PC

@cathoderay esphome can run with encryption. default is non encrypted but its just a config option. wifi, I get it, it does depend on the quality o...

3 years ago
Reply
RE: Heat pump delta T too low - 2c

@william1066 I'm exactly same as you. keen DIYer' . I'd prefer it if the filters came with 28mm connections, but those are all too small bore inside. ...

3 years ago
Reply
RE: Connecting to Midea MSmartHome using a PC

@cathoderay there are different ways to physically do this: it depends on what is where. you need something that is basically a PC (a large one, a s...

3 years ago
Reply
RE: Heat pump delta T too low - 2c

@william1066 3.6m3/h with a DP of 0.22mh20 means its not relying on a monster pump. the chart is here I was comparing to some of the usual suspect ...

3 years ago
Reply
RE: Heat pump delta T too low - 2c

@william1066 doing some component research over the weekend. spirotech 1 1/4 " pressure loss spec took some hunting down but its 2.2kpa (0.22 m...

3 years ago
Reply
RE: Retrofitting: moving to ASHP old oil boiler in large old property - experience/advice please on MSC calcs

@katcesca you've missed something. you do not need to have an EV to access TOU tariffs like octopus Go (12p/unit 4hr offpeak) - despite what some of t...

3 years ago
Reply
RE: Retrofitting: moving to ASHP old oil boiler in large old property - experience/advice please on MSC calcs

TLDR: I nearly fell off my chair when I saw your cost for radiators and fittings. That said, it matches with the ballpark that a number of "ASHP com...

3 years ago
Reply
RE: Convector options for a small kitchen

thats exactly what I've done already. This pushes air through the center of a slightly undersized radiator and makes a noticeable difference to its ou...

3 years ago
Reply
RE: Heat pump delta T too low - 2c

@heacol so if I'm going to replumb in a couple of weeks will you be selling by that point, or just get a bellimo from JTM?

4 years ago
Reply
RE: 15mm piping and the need for flow separation

@william1066 are saying you able to adjust the HP's target DT directly on the samsung? If as per the OP, you knew your system wasn't able to cope wi...

4 years ago
Reply
RE: Heat pump delta T too low - 2c

@william1066 I think the bellimo valves that @heacol recommends are back in stock at JTM, I'm tempted to grab one for my build before he gets them all...

4 years ago