Joining the Renewable Heating Hub forums is completely free and only takes a minute. By registering you’ll be able to ask questions, join discussions, follow topics you’re interested in, bookmark useful threads and receive notifications when someone replies. Non-registered members also do not have access to our AI features. When choosing your username, please note that it cannot be changed later, so we recommend avoiding brand or product names. Before registering, please take a moment to read the Forum Rules & Terms of Use so we can keep the community helpful, respectful and informative for everyone. Thanks for joining!

cathodeRay
cathodeRay
@cathoderay
Moderator
Famed Member
Joined: Feb 28, 2022
Last seen: Sep 6, 2026
Topics: 18 / Replies: 3002
Reply
RE: The good, the bad and the not that great – my heat pump installation

@burtis - we can see the flow rate stays much the same throughout, and the LWT/RWT rise (from 39/32 to 59/52, about what I would expect for a DHW rehe...

2 years ago
Reply
RE: In the Bleak Midwinter... Midea heat pump performance, poor COP and windchill in action

No you're not confused! There are actually two problems visible here: (1) heat pump can't quite cope during periods of low OATs (IAT falls and stays...

2 years ago
Reply
RE: In the Bleak Midwinter... Midea heat pump performance, poor COP and windchill in action

Yes, though it is very tedious and boring doing it. I have a python script that does it manually over modbus (by manually, I mean I have to set the ne...

2 years ago
Reply
RE: In the Bleak Midwinter... Midea heat pump performance, poor COP and windchill in action

Another chart showing the Midea heat pump can't quite cope in cold weather. Blue upper chart is outside air temp (OAT), lower green chart is indoor ai...

2 years ago
Reply
RE: Baffled by heat pump size/ choice!

Yes that can be done, but why do it? If you want a pint jug of water at 40 degrees C, there's no need to boil a kettle, and then dilute the 100 degree...

2 years ago
Reply
RE: Baffled by heat pump size/ choice!

Welcome to the forum! This is getting too hot - you might end up cooking one of the nippers (if they are nippers). The showers might be OK - unti...

2 years ago
Reply
RE: The good, the bad and the not that great – my heat pump installation

@transparent - here's the page with more details and images on what my heat pump has.

2 years ago
Reply
RE: The good, the bad and the not that great – my heat pump installation

@transparent - I summarised the results here. What we actually found were wiring diagrams showing the PWM control cable (in addition to the power cabl...

2 years ago
Reply
RE: The good, the bad and the not that great – my heat pump installation

@burtis - what seems to be happening in both our heat pumps is the flow rate is somehow capped at the lower end of their respective ranges, with the r...

2 years ago
Reply
RE: The good, the bad and the not that great – my heat pump installation

If you know when it will go into DHW heating mode (because it is on a timer?) then it won't take much to get useful readings, say flow rate, LWT/RWT (...

2 years ago
Reply
RE: The good, the bad and the not that great – my heat pump installation

There is also enough info there to calculate calculate power output, which is LWT/RWT delta t x flow rate/3.6 x circulating fluid specific heat (the d...

2 years ago
Reply
RE: The good, the bad and the not that great – my heat pump installation

If you get this in time, can you do some more screen grabs as the water continues to heat. It would be particularly useful to see what the heat pump c...