Joining the Renewable Heating Hub forums is completely free and only takes a minute. By registering you’ll be able to ask questions, join discussions, follow topics you’re interested in, bookmark useful threads and receive notifications when someone replies. Non-registered members also do not have access to our AI features. When choosing your username, please note that it cannot be changed later, so we recommend avoiding brand or product names. Before registering, please take a moment to read the Forum Rules & Terms of Use so we can keep the community helpful, respectful and informative for everyone. Thanks for joining!

Aksel
@aksel
Member
New Member
Joined: Dec 12, 2023
Last seen: Feb 21, 2024
Topics: 1 / Replies: 4
Reply
RE: Daikin Altherma 3 8kW not working as much as needed

Hi!Yes, I needed to go to installation user and then set "Minimum set point" to 37, after that room is warm again.Thread can be locked.

2 years ago
Reply
RE: Daikin Altherma 3 8kW not working as much as needed

Thanks for the response! I think in Daikin Altherma 3 the leaving water temperature is "Minimum set point"? After I set that to 37, our room is ...