Joining the Renewable Heating Hub forums is completely free and only takes a minute. By registering you’ll be able to ask questions, join discussions, follow topics you’re interested in, bookmark useful threads and receive notifications when someone replies. Non-registered members also do not have access to our AI features. When choosing your username, please note that it cannot be changed later, so we recommend avoiding brand or product names. Before registering, please take a moment to read the Forum Rules & Terms of Use so we can keep the community helpful, respectful and informative for everyone. Thanks for joining!
Last seen: Feb 13, 2024
I do so via Home Assistant and the modbus interface to the Samsung Heat Pump - but takes some effort to setup. In any case the Samsung wired remote i...
Generally not my experience, but then I have not ventured much beyond what works with esphome + esp32 and HA. HA does try to make sure the product i...
Minimum volume should be in the specs and seems related to size of heat pump. Volume is important for defrost cycles, which use the heat in the water...
I am not sure where you get 10 degrees from, in eco mode, the target temp is about 3 degrees less than standard My settings are such that if heat...
settings for the DHW. [/quote] Here is my flow temp and hot water tank temperature. I have the same Samsung HP and Controller as you. The diagr...
Keeping this simple - COP is [directly] a function of only two parameters COP = f(ambient outside temp, flow temperature), without moving location yo...
Try this video. There is a link to the spreadsheet, this looks pretty comprehensive, though I did not validate it.
Well, the flow meter comes with the heat pump and I installed an interface into the heat pump to monitor this. My flow rate is currently impacted by ...
The installer may have changed the default, see the manual extract below.
As Ian said, I would not be using forced mode, it disables heating. Try economic, if that does not work, then standard. Standard will use the heat p...
@derekdeleon It looks like they got the connections right, but you probably don't have enough surface area. The BA-16-24 has a Heat Exchange Area: 0...
You need to look at the flow rates in each circuit or pay someone to do the design for you.... AND then explain it to you. What is your overall heat ...