Search with Wattson
Activity
 
Notifications
Clear all

Joining the Renewable Heating Hub forums is completely free and only takes a minute. By registering you’ll be able to ask questions, join discussions, follow topics you’re interested in, bookmark useful threads and receive notifications when someone replies. Non-registered members also do not have access to our AI features. When choosing your username, please note that it cannot be changed later, so we recommend avoiding brand or product names. Before registering, please take a moment to read the Forum Rules & Terms of Use so we can keep the community helpful, respectful and informative for everyone. Thanks for joining!

trebor12345
trebor12345
@trebor12345
Member
Reputable Member
Joined: Feb 26, 2024
Last seen: Aug 1, 2026
Topics: 18 / Replies: 179
Reply
Reply
RE: Replacing my 18 month old Hitachi Yutaki ASHP

JamesPa You will be please to know that this afternoon WE made the DIL switch change to give us a 2C Thermo OFF time. The change was easy, but stress...

8 months ago
Reply
RE: Replacing my 18 month old Hitachi Yutaki ASHP

The Thermo Off (not Thermal Off) only relates to the latest SW installed by Hitachi. To change the Thermo Off setting you have to go into the control...

8 months ago
Reply
RE: Replacing my 18 month old Hitachi Yutaki ASHP

@jamespa The new sw was to prevent rapid short cycles which we were seeing every 3 to 5 minutes. BTW. Heating ticking away at 50% Night Setting. N...

8 months ago
Reply
RE: Replacing my 18 month old Hitachi Yutaki ASHP

I could do the change, I do have an electronics background. But due to health reasons, I am just not confident in doing such things. He does have t...

8 months ago
Reply
RE: Replacing my 18 month old Hitachi Yutaki ASHP

@jamespa No its a chargeable visit. So be at least £200.

8 months ago
Reply
RE: Replacing my 18 month old Hitachi Yutaki ASHP

@jamespa I have good news. I now have the instructions for: Thermo Off. This can be changed to 2C or OFF. I think I will go with the 2C option....

8 months ago
Reply
RE: Replacing my 18 month old Hitachi Yutaki ASHP

@jamespa Looking at setting up the weather compensation. I know from the building that 32C is fine for temperatures below 0C and 5C. But don’t k...

8 months ago
Reply
RE: Replacing my 18 month old Hitachi Yutaki ASHP

JamesPa Below is the plot of yesterdays run (30 Nov). Surprise NO THERMO OFFS. Ran for 10.5 hours. Im afraid it's a fluke!!! I have always expre...

8 months ago
Reply
RE: Replacing my 18 month old Hitachi Yutaki ASHP

JamesPa. Thats one thing that I do have right. Cross that one off the list.  

8 months ago
Reply
RE: Replacing my 18 month old Hitachi Yutaki ASHP

You always challenge my thinking! I don't specifically know why I think it's too long. My only thought is do other systems/users have that long time...

8 months ago
Reply
RE: Replacing my 18 month old Hitachi Yutaki ASHP

JamesPa Just for information 29th Nov run. Nothing really new, except that these Thermo Off periods are way tooooo long at 1hr 20 mins and 2hrs 20 mi...

8 months ago
Page 9 / 17
Share:

SPONSORS

Join Us!

Installer Finder

Degrees of Separation

Latest Posts

SPONSORS

Members Online

Click to access the login or register cheese
Protected By
Shield Security PRO