oh dear oh dear. 22mm plastic is not a big enough pipe for a distribution trunk for a floor's worth of radiators in a system at ASHP flow rates. if it...
@crimson you could try increasing the pump power on the secondary side, that will increase head and flow rate thus increase your chances of getting a ...
hmm. I'm not liking what I see in picture pipes 2. You can there's a junction between a larger pipe and a smaller. That tells me that probably the...
@crimson pipes acting as radiators can be the issue accounting for temperature drop, but also flow rate. That plastic pipe in your picture, hard to ...
@crimson basically - exactly what toodles said! set all TRV's to max (or better, take them off) whilst doing lockshield balancing. The lockshield se...
@crimson have you tried (with all zones and all trv's open) pinching the lockshields down somewhat on the rooms that do heat up well, so as to force m...
@transparent @shaeney I'm impressed by the use of a Spirotech Spirotrap high flow rate low head resistance dirt filter. Its only the second one I've e...
@tobyg sounds good to me. much more likely your house is under 10kw heat loss than over and the lower modulation capability of the grant will help yo...
we're talking about the same thing. If you want to allow your room temps to vary by +-2c you'll need a 3rd party thermostat (thats a 4C swing). Not su...
@peterrsaltings not quite sure why you @'d me into here, I don't run legionella via my controller at all. I heat the whole tank to 55C every day with ...
@tobyg the 1C swing between on and off is native to the samsung controller when used as thermostat. if you want a different window to that, you need t...
you can of course adjust the flow temperature that it runs at post install. But, if you adjust it to lower than what your radiators have been sized fo...
- 23 Forums
- 2,098 Topics
- 46.2 K Posts
- 239 Online
- 3,385 Members
Join Us!
Latest Posts
-
RE: Heating coming on when not required
I played with a max heating temp but there is a world o...
By JamesPa , 11 hours ago
-
RE: Pressure drop Primary circuit
I've always regarded topping up heating systems as my j...
By JamesPa , 11 hours ago
-
RE: Heat pump solutions and/or installer recommendations for France
I’d travel to France for work if you were struggling wi...
By Damon Blakemore , 17 hours ago
-
RE: Ecodan consuming 100kwh per day in new build!!!
Hmm Before doing that I would want to be certain that...
By JamesPa , 23 hours ago
-
RE: 5 Star Service from Havenwise
That's always a danger with any new good idea, @morgan....
By Majordennisbloodnok , 23 hours ago
-
Have your say in the Renewable Heating Hub Awards
It’s time to celebrate the best (and call out the worst...
By Mars , 1 day ago
-
-
RE: Mitsubishi cycling while on chilled water output
@iaack yes there's no denying that cold air sinks! I s...
By downfield , 2 days ago
-
RE: Weather compensated secondary circuits with Biomass
@andycoo that flooring sounds ideal. Extra volume is ...
By Sune , 2 days ago
-
If you are thinking of heating on the immersion conside...
By JamesPa , 3 days ago
-
RE: Surface mount or bury primaries for heat pump installation?
@tomasmcguinness, I think your best bet would be using ...
By Aventus Eco , 3 days ago
-
RE: Solar Power Output – Let’s Compare Generation Figures
@toodles all depends on asking the right questions! And...
By Tim441 , 3 days ago
-
RE: Commencing on an ASHP Installation Process
I received confirmation this morning that my Greener Ho...
By Sheriff Fatman , 4 days ago
-
@jamespa Thanks for the advice - very helpful. I had al...
By abam48 , 5 days ago