Joining the Renewable Heating Hub forums is completely free and only takes a minute. By registering you’ll be able to ask questions, join discussions, follow topics you’re interested in, bookmark useful threads and receive notifications when someone replies. Non-registered members also do not have access to our AI features. When choosing your username, please note that it cannot be changed later, so we recommend avoiding brand or product names. Before registering, please take a moment to read the Forum Rules & Terms of Use so we can keep the community helpful, respectful and informative for everyone. Thanks for joining!

Duncan Mac
@duncan-mac
Contributor
Trusted Member
Joined: Mar 7, 2021
Last seen: Sep 14, 2022
Topics: 1 / Replies: 32
Reply
RE: Vaillant AroTherm 7kW Air Source Heat Pump

@derek-m Hi Derek, just a wee query. Since I have Flow temperatures and outside temperatures at 2 min intervals, if I plot these on a graph, if th...

4 years ago
Reply
RE: Vaillant AroTherm 7kW Air Source Heat Pump

@derek-m thank you sorry again for being such a pain.

4 years ago
Reply
RE: Vaillant AroTherm 7kW Air Source Heat Pump

@derek-m sorry I cant seem to see the attachment you mentioned

4 years ago
Reply
RE: Vaillant AroTherm 7kW Air Source Heat Pump

@derek-m I do have a Vaillant aroTherm 45 liter buffer tank in the system . I have attached the Vaillant Schematic Drawing and I believe my s...

4 years ago
Reply
RE: Vaillant AroTherm 7kW Air Source Heat Pump

@kev-m Thanks for the info. I think you are confirming that I'm not being unrealistic to look for higher COP and SCOP. I still hope Vaillant will...

4 years ago
Reply
RE: Vaillant AroTherm 7kW Air Source Heat Pump

@derek-m this is my MCS spreadsheet. I completed this myself.

4 years ago
Reply
RE: Vaillant AroTherm 7kW Air Source Heat Pump

@derek-m I live in the South West of Scotland and originally I was repeated told that the heat curve should be 1.2, but recently as part of their i...

4 years ago
Reply
RE: Vaillant AroTherm 7kW Air Source Heat Pump

@derek-m I really hope I'm not putting you to any bother Derek. 1a) the COP via the Vaillant sensoApp is calculated by dividing the sum of Electr...

4 years ago
Reply
RE: Vaillant AroTherm 7kW Air Source Heat Pump

@derek-m I don't have thermostats but I do have a Vaillant sensoComfort which I believe acts as some kind of thermostat. It is used to set temperat...

4 years ago
Reply
RE: Vaillant AroTherm 7kW Air Source Heat Pump

@derek-m thanks for that. I'm pretty sure it is in "weather compensation mode "as it cuts out when outside temperature goes above 21degrees and its ...

4 years ago
Reply
RE: Vaillant AroTherm 7kW Air Source Heat Pump

Thanks for the info I will research further. From the information I am getting my system has never drawn more than 4kW at any time since the install. ...

4 years ago
Reply
RE: Vaillant AroTherm 7kW Air Source Heat Pump

I am no Heating engineer but I think there are a number of things to consider here 1) the MCS Heat Loss calculation is for the entire house. I have ...