Joining the Renewable Heating Hub forums is completely free and only takes a minute. By registering you’ll be able to ask questions, join discussions, follow topics you’re interested in, bookmark useful threads and receive notifications when someone replies. Non-registered members also do not have access to our AI features. When choosing your username, please note that it cannot be changed later, so we recommend avoiding brand or product names. Before registering, please take a moment to read the Forum Rules & Terms of Use so we can keep the community helpful, respectful and informative for everyone. Thanks for joining!

DavidB
@davidb
Member
Trusted Member
Joined: Jan 30, 2026
Last seen: Jun 13, 2026
Topics: 6 / Replies: 51
Reply
RE: Need help maximising COP of 3.5kW Valiant Aerotherm heat pump

@jamespa Thanks for the commentary and reassuring comparisons with your own much larger system. The energy consumed of 281kWhrs produced heat of 893...

4 months ago
Reply
RE: Vaillant Tech Support Flagged Low DT: UFH Return Cold, Suspected Zero Flow

@editor thanks for the tips which I will try before calling my installer on Monday. Again much appreciated.

4 months ago
Reply
RE: Need help maximising COP of 3.5kW Valiant Aerotherm heat pump

Yield info for January. I live on a Scottish island.

4 months ago
Reply
RE: Need help maximising COP of 3.5kW Valiant Aerotherm heat pump

Thanks for requesting this info - I hadn’t seen this data before. Live and learn. Not sure if 1000 cycles is good or bad or period of measurement.

4 months ago
Reply
RE: Vaillant Tech Support Flagged Low DT: UFH Return Cold, Suspected Zero Flow

Update - I have been checking the UFH return manifold, waiting on a rise in temperature. Response was fairly slow so I figured the heat was being abs...

4 months ago
Reply
RE: Vaillant Tech Support Flagged Low DT: UFH Return Cold, Suspected Zero Flow

@steelbadger yes, HP running “normally” and, if you have seen some of my other thread, I have no stove burning. I have the system in active mode - so...

4 months ago
Reply
RE: Vaillant Tech Support Flagged Low DT: UFH Return Cold, Suspected Zero Flow

@editor so simple, thanks. Reevaluating what I was seeing, the valve was only just cracked open. It meant the flow pipe was warm a meter away from th...

4 months ago
Reply
RE: Need help maximising COP of 3.5kW Valiant Aerotherm heat pump

@adrian thanks for the explanation Adrian. Sounds as if I should experiment with pure weather compensation for a day or 2, keep the stove off and see...

4 months ago
Reply
RE: Need help maximising COP of 3.5kW Valiant Aerotherm heat pump

@jamespa thanks to both you and Adrian for the comments and suggestions. In one regard I am confused about your comments on our wood burner and impac...

4 months ago