Joining the Renewable Heating Hub forums is completely free and only takes a minute. By registering youâll be able to ask questions, join discussions, follow topics youâre interested in, bookmark useful threads and receive notifications when someone replies. Non-registered members also do not have access to our AI features. When choosing your username, please note that it cannot be changed later, so we recommend avoiding brand or product names. Before registering, please take a moment to read the Forum Rules & Terms of Use so we can keep the community helpful, respectful and informative for everyone. Thanks for joining!
Last seen: Jan 28, 2026
Hi @iancalderbank , Swapped over probes looked like a similar diff initially, but now since running speed 3 on secondary pump these temps seem to ha...
Other photos seem to show a size diff that would indicate 28mm main or more, then 22mm, then 15mm copper at the end. The 22mm branches seem to be for...
Thanks @iancalderbank - waiting for the plumber to confirm the sizing as that was just the builder's guess
@iancalderbank - builder believes it's a standard 22mm flow and return into a 15mm drop for the rads. But is confirming with the plumbers
So all in all I see: Top right of LLH versus pipe in plant room leading to heating zone: 1C drop Total drops with drop from zone pipe to r...
Thanks Ian, I'll ask this with the plumbers. I think upstairs looks to be running of this also, as I know that's approx where a rad is above this ro...
Hi Toodles, don't think any outside. The plant room is all lagged. And the ASHP has a pretty heavy duty underground insulated set (I think further b...
From photos I have of when the project was in progress looks like the pipe work is in the ceilings, plastic, then runs down the walls are metal. Thos...
Thanks Toodles.Here's probably a stupid question. I notice: (Grant panel) LWT on Grant panel (I think this never shows .5C rounded to nearest 1)...
Thanks Toodles, I hope so for sure. That 1.5C max uplift to LWT puts about 1C extra into the system at current temps, and really felt that upstairs. ...
I think itâs safe to say the rads downstairs appear to be the issue. Keeping upstairs on but reducing lock shields down does seem to have reduced cy...
thanks Derek. Iâll try and push for the LLH to volumiser as well as simplification of zones. The DHW cycle heating upstairs was an oversight of the he...