Joining the Renewable Heating Hub forums is completely free and only takes a minute. By registering you’ll be able to ask questions, join discussions, follow topics you’re interested in, bookmark useful threads and receive notifications when someone replies. Non-registered members also do not have access to our AI features. When choosing your username, please note that it cannot be changed later, so we recommend avoiding brand or product names. Before registering, please take a moment to read the Forum Rules & Terms of Use so we can keep the community helpful, respectful and informative for everyone. Thanks for joining!

SUNandAIR
SUNandAIR
@sunandair
Member
Honorable Member
Joined: Dec 30, 2022
Last seen: Mar 21, 2026
Topics: 5 / Replies: 564
Reply
RE: Ecodan cycling

Hi… Sorry I was out last night and missed your post. Thanks for confirming you have a rad output of 12000 watts. My calculation method appears to w...

3 years ago
Reply
RE: Ecodan cycling

Thanks for your reply... it’s a good sign you’re getting a COP of 4 and operating an open loop system. So my first sentence asked what is the rated o...

3 years ago
Reply
RE: Ecodan cycling

Whats the dt50 value of all your radiators? Also, when you observed the cycling how much of your rad system where closed eg. Thermostatic controlled? ...

3 years ago
Reply
RE: Freeze Stat/Defrost setting….Ecodan in freezing conditions

@walkers-heatpump agree. From a practical point of view your comments make sense…. I guess the key is to check the outside pipes are fully insulated r...

3 years ago
Reply
RE: Low flow rate on Samsung Gen6 12KW heat pump

Thanks Derek. Lots of variables to consider. And another reason to try to get the right size heat pump and right size emitter set. Is it also time to ...

3 years ago
Reply
RE: Low flow rate on Samsung Gen6 12KW heat pump

Hi Ian, I think you’re mistaking me for the OP...😉 But you’re right the tables produced seem to suit boiler installations rather than the lower fl...

3 years ago
Reply
RE: Freeze Stat/Defrost setting….Ecodan in freezing conditions

Hi @Linz We have anti freeze valves on our pipes outside. These are usually factory set to bleed at 3degC. This also means we don’t have glycol in o...

3 years ago
Reply
RE: Low flow rate on Samsung Gen6 12KW heat pump

Correction : LWT40 should read DT17.5 eg: LWT40 = DT17.5 : 17kw X 0.255 = 4.3KWh

3 years ago
Reply
RE: Low flow rate on Samsung Gen6 12KW heat pump

Thanks Derek. That clarifies a lot. It has been very useful to work out the DT ratings of radiators when operating at the lower flow temperatures of a...

3 years ago
Reply
RE: Low flow rate on Samsung Gen6 12KW heat pump

hi @derek-m I’ve been looking at your post and recognise what you’re saying and worked out the emitter output for all 7 rads at LWT 50. Can you conf...

3 years ago
Reply
RE: Low flow rate on Samsung Gen6 12KW heat pump

Great sketch also of the pipework @riponowl @iancalderbank has great knowledge of your brand of HP so I’ll keep my comments to pipes and rads. As ...

3 years ago