@craig1980 Hi Craig, Have a look at page 34 onwards which details some test you could carryout on the outdoor unit, should you feel confident. The...
Hi Craig, I'm afraid that I have run out of suggestions. There appears to be something fundamentally wrong with your heat pump, and/or how the sys...
Ignoring any losses, it takes approximately 1.167kWh of energy to raise the temperature of 1000l by 1C. If a heat pump has a flow rate of 25l/min, a...
That is to be expected during the testing. What changes have you made to the Field Setting Values?
@craig1980 Thanks Craig, now lower the LWT setting to 30C and see what happens to how the system operates.
@marzipan71 Hi Steve, Sounds like a good plan. As you may have noticed from many of the forum posts, it is not just in Italy where designers and...
Now measure the top and bottom temperatures on two or three relevant radiators, and the flow rate and temperature readings from the information screen...
@craig1980 How is the system operating now? Is it still running 8 mins on and 20 secs off? What is happening with the room and radiator temps? W...
Yes, that would appear to be the correct method. Try running with a LWT of 35C and see how the system responds, and if it stops the 20 second off peri...
@craig1980 As you say, nothing appears to be changing dramatically. Though I fail to understand how your home is maintaining an indoor temperature o...
@cheshirecat Ask your installer for a detailed list of the equipment that is still to be installed, so that we can check on its availability. Try ...
@craig1980 Thanks, Now try monitoring the 'Master Indoor Zone Information', particularly as the 20 second off period ends and the heat pump restar...
- 26 Forums
- 2,417 Topics
- 54.8 K Posts
- 263 Online
- 6,096 Members
Join Us!
Worth Watching
Latest Posts
-
RE: Octopus Cosy 12 Heat Pump Regret: Incredibly Loud, Poor Heating & Constant Hum - Help!
So, after much anguish, and even visiting the neighbour...
By razz , 6 hours ago
-
MLCP (Multi-Layer Composite Pipe) for ASHP
@editor nope. The info you reported was sufficient for ...
By iotum , 8 hours ago
-
RE: Advice for a novice on Mitsubishi Ecodan 6kW
@robs Quick response while I'm in stationary traffic le...
By Sheriff Fatman , 9 hours ago
-
RE: Setback savings - fact or fiction?
Maths looks right to me, my only question about this ca...
By JamesPa , 9 hours ago
-
RE: Ideal HP290 14kW ASHP - how to optimise
@jamespa I wasn’t offended at all. You are very knowled...
By Davesoa , 9 hours ago
-
RE: Experience - New Build / Complete New Heating System
@vincro I would be surprised if it is much above 5 to 6...
By ASHP-BOBBA , 10 hours ago
-
RE: Recommended home battery inverters + regulatory matters - help requested
Yes, certainly not enough could have been tested in any...
By Batpred , 10 hours ago
-
RE: Post-Traumatic Heat Pump Stress Disorder
Yes bang on and maybe I can illustrate that by way of e...
By iotum , 12 hours ago
-
-
RE: Replacing my 18 month old Hitachi Yutaki ASHP
A big thank you to @jamespa for all his efforts online ...
By trebor12345 , 15 hours ago
-
RE: GSHP WOES! Midland based engineer recommendations?
@editor It is indeed for servicing. My current service ...
By Morgan , 16 hours ago
-
RE: Sunsynk Whole House Backup Issue
Hi @lostandconfused , I agree that topic/thread is the ...
By Batpred , 16 hours ago
-
RE: Speedcomfort radiator fans
In case it helps Andrew Kuhne on openenergy monitor has...
By JamesPa , 17 hours ago
-
Things have gone quiet with you @drei. Any updates?
By Mars , 20 hours ago
-
RE: Passiv Smart Thermostat - Help & Forum Support
Thanks @tim441. Interesting timing, as Passiv are a cur...
By Mars , 21 hours ago
-
Hi everyone, I have a two year old Marlec Solar iBoos...
By Tallmarc , 24 hours ago
-
RE: Please help with the settings ecodan
Are you trying to address any particular performance is...
By Sheriff Fatman , 1 day ago
-
RE: Solis inverters S6-EH1P: pros and cons and battery options
🤣 Well, I never managed to get the HA solis "...
By Batpred , 1 day ago