RE: No spare parts for Vaillant Ground Source Heat Pumps in the UK & major corrosion issue is another problem for GSHP

@phowardstutterheim Correct me if I am wrong, but I assume that you are drawing water out of the bore hole, passing it through the heat exchanger in...

3 years ago
Reply
RE: 17kW Grant Aerona 3 - advice needed for pre-commissioning struggles

If you have a suitable thermometer, I would suggest measuring the temperature of the pipes coming from your ASHP, and also measure the temperature of ...

3 years ago
Reply
RE: 17kW Grant Aerona 3 - advice needed for pre-commissioning struggles

Without looking at the Grant manual, I assume that TM1 is the cold end setting for the weather compensation (WC). Whilst lowering this setting may sav...

3 years ago
Reply
RE: 17kW Grant Aerona 3 - advice needed for pre-commissioning struggles

When you state 'currently running with 40 degrees max', have you set 40C as the maximum permitted LWT?

3 years ago
Reply
RE: 17kW Grant Aerona 3 - advice needed for pre-commissioning struggles

@denevil What are the heat loss calculations and size of your home?

3 years ago
Reply
RE: Connecting to Midea MSmartHome using a PC

I don't think that the data is actually encrypted, more likely coded then decoded. You need to be aware that the serial data transmission is actuall...

3 years ago
Reply
RE: Mitsubishi Ecodan & Raspberry Pi automations

@kev-m Hi Kev, What is the setting of the Interval Timer?

3 years ago
Reply
RE: My ASHP is running out of hot water

Switch off the immersion heater at the wall switch, then using a small spanner remove the nut holding the cover in place. Underneath you should find t...

3 years ago
Reply
RE: Airwell/Midea unit not heating hot water after adjusting weather compensation

I would suggest that you check to see if your system is set for CH priority rather than DHW priority. If so, set it to DHW priority and schedule it fo...

3 years ago
Reply
RE: ashp and pv diverter working together

Electrical power diverters are excellent devices, we have had one connected to our system for quite a number of years. Because they use electronic c...

3 years ago
Reply
RE: My ASHP is running out of hot water

Hi Curly, Do you know where the cable supplying the on - off switch for the immersion heater is supplied from? Can you provide a closeup photo of yo...

3 years ago
Reply
RE: Heat pump delta T too low - 2c

The quantity of heat energy produced by a heat pump is given by the formula:- Q = mcDT Where Q = Heat Energy, m = Mass, c = Specific Heat Capacity...

3 years ago