Joining the Renewable Heating Hub forums is completely free and only takes a minute. By registering you’ll be able to ask questions, join discussions, follow topics you’re interested in, bookmark useful threads and receive notifications when someone replies. Non-registered members also do not have access to our AI features. When choosing your username, please note that it cannot be changed later, so we recommend avoiding brand or product names. Before registering, please take a moment to read the Forum Rules & Terms of Use so we can keep the community helpful, respectful and informative for everyone. Thanks for joining!

cathodeRay
cathodeRay
@cathoderay
Moderator
Famed Member
Joined: Feb 28, 2022
Last seen: Jun 2, 2026
Topics: 18 / Replies: 2921
Reply
RE: 10kw heat pump run in 24*7 data?

As @jamespa says, there is some sort of limitation, or rather imbalance. The difference between the set flow temp and actual flow temp isn't trivial, ...

6 months ago
Reply
RE: 10kw heat pump run in 24*7 data?

Which means the actual flow temp will be less than the set flow temp, and it is was probably also the case in the previous image. You need to catch it...

6 months ago
Reply
RE: 10kw heat pump run in 24*7 data?

Does that image show a target flow temp of 49°, and a current flow temp of 33°C (the images are rather blurred). If so, and it is not in the deep trou...

6 months ago
Reply
RE: 10kw heat pump run in 24*7 data?

I think just a few readings would be useful. Try to pick a time when the OAT is low, and do the same again when it is higher, and you have two points ...

6 months ago
Reply
RE: 10kw heat pump run in 24*7 data?

I think that is an important step, to narrow down where the problem lies, even if you need to do it manually. PS didn't mean to rattle off a lot of ...

6 months ago
Reply
RE: 10kw heat pump run in 24*7 data?

There are still things that don't stack up in this chart (reproduced to avoid the need for page hopping):     Why does the power dro...

6 months ago
Reply
RE: 10kw heat pump run in 24*7 data?

Some observations: 1. I for one don't know the Vaillant jargon and that makes it difficult to comment, or even understand what the problem is. I thi...

6 months ago
Reply
RE: 10kw heat pump run in 24*7 data?

Yes, but that is in cold weather. If you look at my chart, you will see that I was using around 4kW in the middle of the night (ouch!), but middle of ...

6 months ago
Reply
RE: 10kw heat pump run in 24*7 data?

A different heat pump (Midea 14kW) but a stark reminder of what a difference a change in OAT makes to the trailing 60 minute COP (blue line in lower c...