Joining the Renewable Heating Hub forums is completely free and only takes a minute. By registering you’ll be able to ask questions, join discussions, follow topics you’re interested in, bookmark useful threads and receive notifications when someone replies. Non-registered members also do not have access to our AI features. When choosing your username, please note that it cannot be changed later, so we recommend avoiding brand or product names. Before registering, please take a moment to read the Forum Rules & Terms of Use so we can keep the community helpful, respectful and informative for everyone. Thanks for joining!

BobTSkutter
@bobtskutter
Member
Estimable Member
Joined: Jan 11, 2025
Last seen: Jan 6, 2026
Topics: 1 / Replies: 93
Reply
RE: Is My Midea Heat Pump Inherently Defective?

@cathoderay this is great news. I'm pleased we're getting somewhere. There's a noticeable step change in the power output starting with the 18:00 re...

1 year ago
Reply
RE: Is My Midea Heat Pump Inherently Defective?

Hello, Sounds like the flow goes through the magnetic filter before it gets to the PEX, so that's good. 22mm and 1.8m3/hr is about 1.3m/s. I thin...

1 year ago
Reply
RE: Is My Midea Heat Pump Inherently Defective?

A brief explanation of reading vendor pump curves. Here's a simple heating system. It's got 3 radiators, each one can be turned on or off separatel...

1 year ago
Reply
RE: Is My Midea Heat Pump Inherently Defective?

Something else crossed my mind when I posted on a discussion about the order components should installed. You mentioned you reversed the direction o...

1 year ago
Reply
RE: Is My Midea Heat Pump Inherently Defective?

Hello All,I'm conscious I've turned up on the forum and am writing these long posts full of apparent technical detail. I've been troubleshooting heat ...

1 year ago
Reply
RE: Mixing of pipework/components' with different internal dimensions - theory vs reality/practical approach

Hello All, remember your designing a loop transferring liquid water. The pump just moves the liquid round in circles. It makes no difference to syst...

1 year ago
Reply
RE: Is My Midea Heat Pump Inherently Defective?

@cathoderay I'll put something together about pump curves and system curves. But to help you, I suggest the following: Open all the TRVs and locks...

1 year ago
Reply
RE: Is My Midea Heat Pump Inherently Defective?

Hello, I can explain all the pump curve information, but it will take a while for me to put some pictures together. For now, lets work on the basis t...

1 year ago
Reply
RE: Is My Midea Heat Pump Inherently Defective?

^Hey, look at that, it worked 🙂 OK, This is a pump curve. The top one shows Head against volumetric flow at different pump speeds. The chart show...

1 year ago
Reply
RE: Is My Midea Heat Pump Inherently Defective?

Hello again,I wonder what's going on here? The system seems to have landed at an equilibrium point. LWT = Set_LWT and the compressor has slowed do...

1 year ago
Reply
RE: Is My Midea Heat Pump Inherently Defective?

Hello,I'm not very good with using quotes from forum posts, so I'll try to use headings insted.How did I calculate the secondary flow rate?If you igno...

1 year ago
Reply
RE: Is My Midea Heat Pump Inherently Defective?

I found an install manual for an MD16IU-008DW unit. Can you find the value of dT1SH? It might be in "ServiceMan / 3. Heat mode settings" The manu...