RE: Grant 13kW Aerona3 - issues getting zones to temp

Thanks @crimson, buried primary piping looks a proper product, probably Isoflow or similar. Good. Primary flow must be fixed #1 priority. Clean stra...

2 years ago
Reply
RE: Grant 13kW Aerona3 - issues getting zones to temp

@crimson good morning. Lots of people here want this one fixed for you! What's the approximate length of buried pipework on the primary circuit under ...

2 years ago
Reply
RE: Grant 13kW Aerona3 - issues getting zones to temp

Hi @crimson, sure. The formula is the sensible heat equation, to work out how much heat energy in kJ/s is being added. 9 is your flow rate as indica...

2 years ago
Reply
RE: Grant 13kW Aerona3 - issues getting zones to temp

@crimson great stuff. The delta T between flow and return is high, especially when your ASHP is on low load, 1300W power consumption, that's about 1/3...

2 years ago
Reply
RE: Grant 13kW Aerona3 - issues getting zones to temp

@Crimson, I hesitate to state it, but it seems like your plumbers are clueless. You need a fresh pair of eyes on the job as there's something seriousl...

2 years ago
Reply
RE: Grant 13kW Aerona3 - issues getting zones to temp

Finally Grant is waking up and smelling the coffee and, when they offer their 'smart controller' option pack (which monitors primary flow rate), they ...

2 years ago
Reply
RE: Grant 13kW Aerona3 - issues getting zones to temp

Hi @crimson, probably time to bite the bullet and get the system checked over by Grant. The installation manual from Grant has suggested circuits for ...

2 years ago
Reply
RE: Grant 13kW Aerona3 - issues getting zones to temp

Some progress on the hot water. Reducing the flow on the secondary side to balance with the deficient flow on the primary side is a sticking plaster. ...

2 years ago
Reply
RE: Grant 13kW Aerona3 - issues getting zones to temp

@crimson small steps towards a resolution. The flow rate is a biggie, that needs fixing. That will be throwing a spanner in the works in the LLH if th...

2 years ago
Reply
RE: Grant 13kW Aerona3 - issues getting zones to temp

Hi @crimson, the flow rate is constant for Grant systems, as they have a fixed speed pump in the ASHP. If your primary flow rate is 9l/min, and the fl...

2 years ago
Reply
RE: Grant 13kW Aerona3 - issues getting zones to temp

@crimson - is that flow rate photo taken with the ASHP running? It's showing a flow rate about 9 litres/minute. If so, that's way below Grant's minimu...

2 years ago
Reply
RE: Grant 13kW Aerona3 - issues getting zones to temp

Most Grant Aerona ASHPs work on a DT of 5degC, they will push up to 8degC, but seem happiest with a low DT. If you are in the habit of turning the hea...

2 years ago