As a rough comparison I had 3 quotes in Nov 2020 for: 14Kw Mitsubishi Ecodan pump 250l DHW tank 6 new radiators MMSP One came in at £14K and...
No it's FTC6 PAC-IF072B-E
They come from the MelCloud app (part of the MMSP). There is a phone version and web browser version. Temperature History is useful for DHW tank tem...
Yes the DHW reached 51º and the value closed properly. I'll keep my eye on that this week. As the for flow temp, at 40º set this morning the UFH are...
@derek-m Aha! It seems the motor had gotten jammed. After quick manual turning of the little cog with some pliers the valve seems to open and close ...
I've just tried that on another valve that controls flow to the radiators and yes manually opening it (move to the left) is quickly followed by an aut...
Thanks for your suggestion Brendon. You clearly have a comprehensive understanding of ASHP systems.I imagine swapping out that valve in isolation woul...
The lever is loose. i.e. I can movie left to right meaning it is open. As a test this morning when the DHW was at 35º I turned off the DHW heating, ...
It's possibly an FTC6 looking at the product number and date of manufacture (see sticker). No there is no wired or wireless sensor attached. No th...
Thanks Derek. Your time is very much appreciated. That is correct, it's on a flow temp setting and several thermostats control the calling for heat....
More granular data for the PUZ-HWM140VHA
I managed to find some data although not as granular as your charts. For the Mitsubishi Ecodan 14Kw R32 PUZ-HWM140VHA model it states that at 7º outsi...
- 26 Forums
- 2,417 Topics
- 54.8 K Posts
- 395 Online
- 6,096 Members
Join Us!
Worth Watching
Latest Posts
-
RE: Recommended home battery inverters + regulatory matters - help requested
That's something which DESNZ isn't considering, and is ...
By Transparent , 2 minutes ago
-
RE: Fan unit Making terrible noise HELP!!
@gutoffowc Oh no, sorry to hear that, are you in the Ke...
By ASHP-BOBBA , 40 minutes ago
-
RE: Ideal HP290 14kW ASHP - how to optimise
Thanks everyone so much for your replies and help. Last...
By cmartinbwmba , 43 minutes ago
-
RE: Sunsynk Whole House Backup Issue
@sheriff-fatman - could you please re-post that in the ...
By Transparent , 1 hour ago
-
RE: Advice for a novice on Mitsubishi Ecodan 6kW
@robs Just to quickly fill in some of the gaps in the r...
By Sheriff Fatman , 2 hours ago
-
RE: Running my new Nibe ASHP efficiently
I didn't. I spent a while manually messing around with ...
By jamieheatpumpnew , 3 hours ago
-
Hi, I think I’m having some issues with my Ecodan as...
By Patch321 , 3 hours ago
-
RE: I’m glad the cold spell is over!
I comparison with the 65kWh used above yesterday was on...
By Judith , 3 hours ago
-
RE: New Daikin 11kW Altherma 3M install - is it working as it should?
@synthbuilder Further to the above…‘What a difference t...
By Toodles , 4 hours ago
-
RE: Octopus Cosy 12 Heat Pump Regret: Incredibly Loud, Poor Heating & Constant Hum - Help!
I should think so, I thought that pretty much universal...
By JamesPa , 4 hours ago
-
RE: Setback savings - fact or fiction?
I'm also inclined to look into how a defrost is actuall...
By cathodeRay , 4 hours ago
-
MLCP (Multi-Layer Composite Pipe) for ASHP
@editor nope. The info you reported was sufficient for ...
By iotum , 15 hours ago
-
RE: Experience - New Build / Complete New Heating System
@vincro I would be surprised if it is much above 5 to 6...
By ASHP-BOBBA , 16 hours ago
-
RE: Post-Traumatic Heat Pump Stress Disorder
Yes bang on and maybe I can illustrate that by way of e...
By iotum , 18 hours ago
-
-
RE: Replacing my 18 month old Hitachi Yutaki ASHP
A big thank you to @jamespa for all his efforts online ...
By trebor12345 , 21 hours ago
-
RE: GSHP WOES! Midland based engineer recommendations?
@editor It is indeed for servicing. My current service ...
By Morgan , 22 hours ago
-
RE: Speedcomfort radiator fans
In case it helps Andrew Kuhne on openenergy monitor has...
By JamesPa , 23 hours ago