Search with Wattson
Activity
 
Notifications
Clear all

Joining the Renewable Heating Hub forums is completely free and only takes a minute. By registering you’ll be able to ask questions, join discussions, follow topics you’re interested in, bookmark useful threads and receive notifications when someone replies. Non-registered members also do not have access to our AI features. When choosing your username, please note that it cannot be changed later, so we recommend avoiding brand or product names. Before registering, please take a moment to read the Forum Rules & Terms of Use so we can keep the community helpful, respectful and informative for everyone. Thanks for joining!

cathodeRay
cathodeRay
@cathoderay
Moderator
Famed Member
Joined: Feb 28, 2022
Last seen: Sep 7, 2026
Topics: 18 / Replies: 3012
Reply
RE: Midea ASHP Install & Potential Changes

@dons - no, you are not going mad, it is just Midea playing language games! On the wired controller screen, you have POWER CONSUM, which is the total ...

3 years ago
Reply
RE: Midea ASHP Install & Potential Changes

In an ideal world, it wouldn't switch itself off. It runs continuously, adjusting the LWT, based on the WCC, to deliver the right amount of heat to ke...

3 years ago
Reply
RE: Midea ASHP Install & Potential Changes

Ideally, you want the room stat set high enough to ensure the heat pump is always on, and all the other emitter controls fully open, to ensure the sys...

3 years ago
Reply
RE: Performance in the current cold snap…

Sorry, but I want to be clear about this in my own mind. I think it may be all about what happens during the defrost, and how you account for it (in a...

3 years ago
Reply
RE: Performance in the current cold snap…

Yes, I am sure as can be. It is down to simple numbers. The calculated heat loss at -2 is 12.4 kW, a figure that I think is as good an estimate as can...

3 years ago
Reply
RE: Performance in the current cold snap…

Sorry, forgot to include this bit. Yes, will try CC3. I'm also going to put the left had WCC baseline back up to 56, at least for the next 12 hours or...

3 years ago
Reply
RE: Performance in the current cold snap…

Yes, that is the right document. I absolutely get this, but my hands are tied by the design constraints: small area for rads, fitted the largest we co...

3 years ago
Reply
RE: Midea ASHP Install & Potential Changes

I appreciate that, and no harm in doing it, but it helps to have something to focus on, as you have now done. Freedom, who also supplied my Midea he...

3 years ago
Reply
RE: Midea ASHP Install & Potential Changes

@dons - the is quite a lot of info there, but not so much in the way of clear specific questions. It might help if you summarised your key questions, ...

3 years ago
Reply
RE: Performance in the current cold snap…

@iancalderbank - The manual the tables comes from is available online, and can be found using google (midea m thermal mono engineering data pdf). A li...

3 years ago
Page 144 / 253
Share:

SPONSORS

Join Us!

Installer Finder

Degrees of Separation

Latest Posts

SPONSORS

Members Online

Click to access the login or register cheese
Protected By
Shield Security PRO