RE: Midea ASHP – how to set weather compensation

@cathoderay thanks for that. I have set up daily schedule for 13.00-14.00 when I usually have PV power and OAT is higher on average. My controller sho...

4 months ago
Reply
RE: Midea ASHP – how to set weather compensation

@cathoderay and others. So now I am running an open system on WC. House is a little too warm (except the always problematic en suite). As @jamespa sug...

4 months ago
Reply
RE: Midea ASHP – how to set weather compensation

@cathoderay is the tank back-up heater the potential mega-kettle aka buffer tank? I see the mine too on my display occasionally 😀

4 months ago
Reply
RE: Midea ASHP – how to set weather compensation

@batalto what is "the app" you refer to? Ta

4 months ago
Reply
RE: Heat Pump Servicing & Maintenance – Good Value or Rip-Off?

@ashp-bobba wish you lived closer to Wiltshire! My installer charges £294 for a service. Given the issues I have had with my system I believe it's pur...

4 months ago
Reply
RE: Midea ASHP – how to set weather compensation

@cathoderay thanks very much. I seem to be making progress both in my understanding and finding potential future solutions. At the very least the engi...

4 months ago
Reply
RE: Midea ASHP – how to set weather compensation

@cathoderay the dataloggers have been purchased and are on their way. The plan as per your instructions, is to leave one outside for OAT and one insid...

4 months ago
Reply
RE: Midea ASHP – how to set weather compensation

@benson thanks. @cathoderay suggests using data loggers to collect the data. How did you do it? Same method or different?

4 months ago
Reply
RE: Midea ASHP – how to set weather compensation

Lunch over. Back to it Some more observations from discussion with installer. Given they raised possibility that the UFH is not insulated properly (...

4 months ago
Reply
RE: Midea ASHP – how to set weather compensation

@cathoderay thanks. I had a call within half an hour of sending my letter by email. My requests were 1) fix the insulation as per @transparent recom...

4 months ago
Reply
RE: Midea ASHP – how to set weather compensation

@cathoderay I hear you. I have just finished a letter to the company. I have asked for immediate rectification of the insulation issues due to Part L ...

4 months ago