Reply
RE: ASHP Cycling On/Off - Is it an issue?

@saenergy I've altered the curve. Currently running at 28-29C today and the house is plenty warm enough. Would bigger radiators result in an improv...

3 years ago
Reply
RE: ASHP Cycling On/Off - Is it an issue?

@saenergy Thanks for the pointers. Regarding the bypass valve, I assume winding it in will effectively shut it off for now would it? The diver...

3 years ago
Reply
RE: ASHP Cycling On/Off - Is it an issue?

@derek-m & @kev-m Thanks for looking over the report. I was going around in circles a bit with the report too but didn't know if it was me and m...

3 years ago
Reply
RE: ASHP Cycling On/Off - Is it an issue?

@saenergy The auto bypass is located just after the 3 port valve, before any of the radiators. A quick google search suggests it should be located ...

3 years ago
Reply
RE: ASHP Cycling On/Off - Is it an issue

I have posted a link to the report, it's just not showing as one. I'll insert it properly here as I can't edit my original post.

3 years ago
Reply
RE: ASHP Cycling On/Off - Is it an issue

@derek-m forgot to add - agreed on scheduling the time of the hot water run, I did find that improved things. I've already got mine setup for late aft...

3 years ago
Reply
RE: ASHP Cycling On/Off - Is it an issue

@heat-pump-newbie electricity usage is about the same for a comparable day, but heat output is higher, so that's a win. But I've noticed the compresso...

3 years ago
Reply
RE: ASHP Cycling On/Off - Is it an issue

@kev-m Yes, the COP is for both. I didn't use much hot water yesterday, so most of the demand was on the heating. See screenshot below for the last...

3 years ago
Reply
RE: ASHP Cycling On/Off - Is it an issue

@derek-m The cycling is only occurring at outside temperatures above about 8C so probably nothing to worry about. COP for yesterday was 3.18, not b...

3 years ago
Reply
RE: ASHP Cycling On/Off - Is it an issue

@derek-m Still good news I think. I've had about a week of running using the weather compensation curve. The house is definitely warmer, almost too...

3 years ago
Reply
RE: ASHP Cycling On/Off - Is it an issue

@derek-m thanks again for the info. So I sat with the heat pump controller for two hours this evening recording data every five minutes, I can post ...

3 years ago
Reply
RE: Rate your air source heat pump installer

@timh avoid Northern Gas Plumbing and Heating based out of Northampton. They were chosen for me and were rubbish. Fortunately I'm part of a trial whic...

3 years ago
Page 4 / 5
Share:

Join Us!

Heat Pump Dramas?

Thinking about installing a heat pump but unsure where to start? Already have one but it’s not performing as expected? Or are you locked in a frustrating dispute with an installer or manufacturer? We’re here to help.

Pre-Installation Planning
Post-Installation Troubleshooting
Performance Optimisation
✅ Complaint Support (Manufacturer & Installer)

👉 Book a one-to-one consultation now.

Latest Posts

x  Powerful Protection for WordPress, from Shield Security
This Site Is Protected By
Shield Security