RE: Avoid the Heat Pump Villain: Why Low-Loss Headers and Buffers Can Sabotage Your Heat Pump's Efficiency

@potatoman As no one seems to be obliging, I attach a diagram. The idea is that only bypass flow goes through the tank when necessary so it is undistu...

10 months ago
Reply
RE: Hitachi Yutaki SCombi Heat Pump - Thermal Off's

@trebor12345 The Auto function is supposed to adapt automatically and select the right curve in constant pressure mode. By default the pump is set to...

10 months ago
Reply
RE: Hitachi Yutaki SCombi Heat Pump - Thermal Off's

@trebor12345 Your house is remarkably similar to mine, layout included. I have 185 sqms with 4 beds and 2 baths, same size lounge with exactly the sa...

10 months ago
Reply
RE: Hitachi Yutaki SCombi Heat Pump - Thermal Off's

@trebor12345 Use the internal private messaging system on this forum.

10 months ago
Reply
RE: Hitachi Yutaki SCombi Heat Pump - Thermal Off's

@trebor12345 Re your question about changing setting to controlled DT, this may be worth trying if your current DT is 1C as the heat pump will automa...

10 months ago
Reply
RE: Hitachi Yutaki SCombi Heat Pump - Thermal Off's

@trebor12345 There doesn't seem to be anything obvious on the refrigeration cycle as the temperature ups and downs look logical. However your DT is e...

10 months ago
Reply
RE: Hitachi Yutaki SCombi Heat Pump - Thermal Off's

@trebor12345 I can send you a service manual however it is very large (200MB) so exceeds the file size limit here. If you can send me an appropriate ...

10 months ago
Reply
RE: Hitachi Yutaki SCombi Heat Pump - Thermal Off's

@trebor12345 The penny has finally dropped. I thought you were describing defrost sequences. If you say that this happens at 20C OAT, it is not norma...

10 months ago
Reply
RE: Hitachi Yutaki SCombi Heat Pump - Thermal Off's

@trebor12345 @jamespa From the calcs you sent, your house conforms with modern insulation standards e.g. roof u-value 0.11. Your overall heat loss is...

10 months ago
Reply
RE: Hitachi Yutaki SCombi Heat Pump - Thermal Off's

@trebor12345 The heat exchanger function is the same regardless of whether it is inside or outside. Your heat pump is a 7kW unit, not 3kW as per y...

10 months ago
Reply
RE: Hitachi Yutaki SCombi Heat Pump - Thermal Off's

@trebor12345 By way of further explanation, in cooling mode the compression cycle of the heat pump reverses i.e. the gas flow goes in the opposite d...

10 months ago
Reply
RE: Hitachi Yutaki SCombi Heat Pump - Thermal Off's

@trebor12345 Firstly, the brochure description of the Hitachi says that it definitely uses hot gas bypass for defrost as per the process I described...

10 months ago