Reply
RE: Mitsubishi Ecodan ASHP general set-up and efficiency

@ngillam yes but only need to do one at a time unless you live in a mansion with different wings 90 seconds is a long time

6 months ago
Reply
RE: Mitsubishi Ecodon stuck on immersion symbol

@ak2024 the thermistor for the tank temp is low down in the cylinder so as soon as you draw hot water the temp drops rapidly but in reality you have p...

6 months ago
Reply
RE: Mitsubishi Ecodan ASHP general set-up and efficiency

@ngillam you dont need to remove the thermostats to pair them to the wiring centre. if they can't pair in situ then they are too far from the wiring ...

6 months ago
Reply
RE: Mitsubishi Ecodan ASHP general set-up and efficiency

@ngillam yes it just screws in I don't think you even need to take the cover off, if you have 3 ariels do you have 3 different wiring centres?

6 months ago
Reply
RE: Flow temperature- At what point?

@westkent I'm not that familiar with autoadapt as it for use with radiators and I have UFH. I think there may be limitations within the service menu ...

6 months ago
Reply
RE: Mitsubishi Ecodan ASHP general set-up and efficiency

@ngillam Can't really compare houses ours is badly insulated circa 2003 185sqm detached house, 8.5KW heat pump. My flow temp down to 3C is 32C then in...

6 months ago
Reply
RE: Mitsubishi Ecodan ASHP general set-up and efficiency

I believe the UH8 RF wiring centre you have is only compatible with wireless thermostats so I think that confirms they are wireless. Once you ha...

6 months ago
Reply
RE: Flow temperature- At what point?

@westkent Ah your question makes more sense now, auto adapt does use the room temp and uses the weather comp curve set as a starting point but then wi...

6 months ago
Reply
RE: Flow temperature- At what point?

If you are running on weather compensation then room target temp doesn't factor into it, the heat pump will be running 24/7 and your house won't reach...

6 months ago
Reply
RE: Mitsubishi Ecodan ASHP general set-up and efficiency

I would suspect that just because you were told that thermostat is connected to that channel on the wiring centre it isnt. I would turn down all the...

6 months ago
Reply
RE: Mitsubishi Ecodan ASHP general set-up and efficiency

The lights going out means those UFH circuits have closed off as the thermostats that are controlling them have been satisfied, if the rooms are too c...

6 months ago
Reply
RE: Ecodan help - flow temperature spikes when operating in weather compensation mode

@sunandair Yes that duration is just a max you are allowing it to run for, there is also a setting for how long it then has to wait before it can retu...

6 months ago
Page 15 / 29
Share:

Join Us!

Trusted Installers

Struggling to find a reliable heat pump installer? A poor installation can lead to inefficiencies and high running costs. We now connect homeowners with top-rated installers who deliver quality work and excellent service.

✅ Verified, trusted & experienced installers
✅ Nationwide coverage expanding
✅ Special offers available

👉 Find your installer now!

Latest Posts

x  Powerful Protection for WordPress, from Shield Security
This Site Is Protected By
Shield Security