Last seen: Jan 12, 2025
Hi Derek, What a result!!............Changed the pump connector to CNP4 and pump no longer runs unless required by DHW call for heat.........proved i...
@DerekM Hi Derek, I have not yet tried swapping the DHW pump connection over although as you have said and from looking through all online manuals...
@derek-m Thanks for your advice Derek.....my system is out of warranty with the installer so I think I will come clean and let them know I have fou...
@harriup The wiring is not correct and the DHW pump is running all the time the primary pump is running....see latest post to @derekm I only run t...
Hi Derek, Been back up in the loft (Big mistake that was)! , and traced cables from pumps to the FTC board As we suspected the FTC is not wired a...
Hi Derek....no wonder you were not at your peak with the amount of input you contribute to the forums. Your assumption of my query could be correct ...
Agree it looks a bit like a rat's nest!! I think I differ in that I have an external plate heat exchanger (not the internal coil )and the dedicated ...
Derek....if you zoom in I think the model no's can be seen but I can clarify the auto pump is UPM3 Auto L(think this is the heating circuit pump)........
The unit came all prewired and plumbed from Mitsubishi so it sounds like it has to be as you have said...I think I will give mitsubishi a call on this...
Hi Derek, Photos as requested, the pump without any obvious manual control is the one adjacent to the one with LED display(the one that data sheets ...
@Sun&Air...thanks for your comments......a lot of water has passed under the bridge since I posted back on page 5 so things have got a bit disjoi...
@derekm and everyone else 😄 I said that I would investigate in more detail what is happening with my full mitsubishi packaged system pumps and have ...
- 22 Forums
- 2,037 Topics
- 44.4 K Posts
- 28 Online
- 3,250 Members
Join Us!
Trusted Installers
Struggling to find a reliable heat pump installer? A poor installation can lead to inefficiencies and high running costs. We now connect homeowners with top-rated installers who deliver quality work and excellent service.
✅ Verified, trusted & experienced installers
✅ Nationwide coverage expanding
✅ Special offers available
Latest Posts
-
RE: Help with understanding my Mitsubishi Ecodan air source heat pump
Welcome to the forum@patch and well done for your under...
By Judith , 58 minutes ago
-
RE: Air Source Heat Pump - Side Alley Suitability
@jamespa I used an assumed indoor temperature of 18C. I...
By Ad3628 , 3 hours ago
-
RE: ASHP Ecodan L9 error - No Heating but Hot Water
That’s interesting, but obviously concerning also…. Do ...
By SUNandAIR , 4 hours ago
-
RE: In the middle of an ASHP installation - a few questions (and issues)
Thank you @robs - that very useful data. The issue wa...
By Transparent , 7 hours ago
-
RE: The Rise and Fall of Europe’s Most Generous Green Subsidy
@editor Attached images of external insulation. Think...
By Dwynwen , 13 hours ago
-
RE: Hitachi Yutaki SCombi Heat Pump - Thermal Off's
@trebor12345 The Auto function is supposed to adapt au...
By Heatgeek , 1 day ago
-
RE: The Great British Heat Pump Quiz
@allyfish thanks for the feedback and glad it was fun! ...
By Mars , 1 day ago
-
RE: help sizing rads based on room by room heat loss
If its 1988W at DT 50, which is how most radiators are ...
By JamesPa , 2 days ago
-
RE: Career change – entering the world of heating and heat pumps
@editor Mars, thank you. That's along the routes I was ...
By Lakey , 2 days ago
-
@editor thanks Mars, it's a rare occasion I'm looking f...
By big_si , 2 days ago
-
RE: Efficiency Concerns on newly installed Mitsubishi Ecodan 8.5kW
@ashp-bobba and @jamespa - thank you both for all your ...
By CBrenewable , 2 days ago
-
-
Win one of five "Heat Pumps 101" Courses
Heat pumps are gaining traction in the UK, but between ...
By Mars , 2 days ago
-
RE: Agile: average import cost vs other tariffs?
@toodles thanks for the analysis. I'll be really intere...
By Old_Scientist , 3 days ago
-
RE: Is this normal? Click of the DHW returning to space heating
@grantmethestrength Oh sorry to hear that, there should...
By ASHP-BOBBA , 3 days ago
-
@ashp-bobba TBH the ladies are rather disorganised, so ...
By Cathyem1 , 3 days ago
-
RE: Solar Power Output – Let’s Compare Generation Figures
And for those of us without an automatic irrigation sys...
By Majordennisbloodnok , 3 days ago
-
Logically, the lower frequency = more gentle, yes, but ...
By SUNandAIR , 3 days ago
-
RE: Ideal Logic ASHP - change from 55°C to 35°C Heating?
Good point. I’ll keep my eye on the manifold temperatur...
By Tomdad , 4 days ago