Hi Derek, What a result!!............Changed the pump connector to CNP4 and pump no longer runs unless required by DHW call for heat.........proved i...
@DerekM Hi Derek, I have not yet tried swapping the DHW pump connection over although as you have said and from looking through all online manuals...
@derek-m Thanks for your advice Derek.....my system is out of warranty with the installer so I think I will come clean and let them know I have fou...
@harriup The wiring is not correct and the DHW pump is running all the time the primary pump is running....see latest post to @derekm I only run t...
Hi Derek, Been back up in the loft (Big mistake that was)! , and traced cables from pumps to the FTC board As we suspected the FTC is not wired a...
Hi Derek....no wonder you were not at your peak with the amount of input you contribute to the forums. Your assumption of my query could be correct ...
Agree it looks a bit like a rat's nest!! I think I differ in that I have an external plate heat exchanger (not the internal coil )and the dedicated ...
Derek....if you zoom in I think the model no's can be seen but I can clarify the auto pump is UPM3 Auto L(think this is the heating circuit pump)........
The unit came all prewired and plumbed from Mitsubishi so it sounds like it has to be as you have said...I think I will give mitsubishi a call on this...
Hi Derek, Photos as requested, the pump without any obvious manual control is the one adjacent to the one with LED display(the one that data sheets ...
@Sun&Air...thanks for your comments......a lot of water has passed under the bridge since I posted back on page 5 so things have got a bit disjoi...
@derekm and everyone else 😄 I said that I would investigate in more detail what is happening with my full mitsubishi packaged system pumps and have ...
- 27 Forums
- 2,495 Topics
- 57.8 K Posts
- 437 Online
- 6,220 Members
Join Us!
Worth Watching
Latest Posts
-
Sorry to bounce your thread. To put to bed some concern...
By L8Again , 2 minutes ago
-
@painter26 — they (the analogue gauges) are subtly diff...
By cathodeRay , 36 minutes ago
-
I cannot see the complete rcbo, since the photo is cut....
By Batpred , 49 minutes ago
-
RE: What determines the SOC of a battery?
The answer from Fogstar was crisp. My hypothesis, su...
By Batpred , 59 minutes ago
-
RE: Electricity price predictions
I am always impressed with how you keep abreast of so m...
By Batpred , 1 hour ago
-
RE: Setback savings - fact or fiction?
I fully understand your reasoning, same steady inputs s...
By cathodeRay , 1 hour ago
-
RE: Humidity, or lack thereof... is my heat pump making rooms drier?
@majordennisbloodnok I’m glad I posted this. There see...
By AndrewJ , 2 hours ago
-
RE: Testing new controls/monitoring for Midea Clone ASHP
@tasos and @cathoderay thanks. I have some history grap...
By benson , 3 hours ago
-
Our Experience installing a heat pump into a Grade 2 Listed stone house
First want to thank everybody who has contributed to th...
By Travellingwave , 4 hours ago
-
RE: Solis inverters S6-EH1P: pros and cons and battery options
Just to wrap this up here for future readers: The S...
By Batpred , 7 hours ago
-
RE: Struggling to get CoP above 3 with 6 kw Ecodan ASHP
Welcome to the forums.I assume that you're getting the ...
By Sheriff Fatman , 7 hours ago
-
RE: Say hello and introduce yourself
@editor @kev1964-irl This discussion might be best had ...
By GC61 , 9 hours ago
-
RE: Oversized 10.5kW Grant Aerona Heat Pump on Microbore Pipes and Undersized Rads
@uknick TBH if I were taking the floor up ...
By JamesPa , 23 hours ago
-
RE: Getting ready for export with a BESS
I would have not got it if it was that tight
By Batpred , 1 day ago
-
RE: Need help maximising COP of 3.5kW Valiant Aerotherm heat pump
@judith thanks Judith. Confirmation appreciated. The ...
By DavidB , 1 day ago
-
RE: Recommended home battery inverters + regulatory matters - help requested
That makes sense. I thought better to comment in this t...
By Batpred , 1 day ago
-
Bosch CS5800i 7kW replacing Greenstar Junior 28i
My heat pump journey began a couple of years ago when I...
By Slartibartfast , 1 day ago
-
RE: How to control DHW with Honeywell EvoHome on Trianco ActiveAir 5 kW ASHP
The last photo is defrost for sure (or cooling, but pre...
By JamesPa , 1 day ago
-
RE: Plug and play solar. Thoughts?
Essentially, this just needed legislation. In Germany t...
By Batpred , 1 day ago
-
RE: A Smarter Smart Controller from Homely?
@toodles Intentional opening of any warranty “can of wo...
By Papahuhu , 1 day ago
-
RE: Safety update; RCBOs supplying inverters or storage batteries
Thanks @transparent Thankyou for your advic...
By Bash , 1 day ago
-
RE: Air source heat pump roll call – what heat pump brand and model do you have?
Forum Handle: Odd_LionManufacturer: SamsungModel: Samsu...
By Odd_Lion , 1 day ago
-
RE: Configuring third party dongle for Ecodan local control
Well, it was mentioned before in the early pos...
By F1p , 2 days ago